Hardware description
22
Overview: Connections
The diagram gives an overview of connections. I/O connections are parameterable.
The diagram shows the default I/O connections for the ABB standard macro. See
chapter
for I/O connections for the different macros and chapter
for installation in general.
DI1
Stop/Start
DI2
Forward/Reverse
DI3
Constant speed
selection
DI4
Constant speed
selection
DI5
Acceler. and
deceler. selection
1)
Digital input common
Aux. voltage output common
+24 V
Aux. voltage output
+24 VDC, max. 200 mA
DOSRC
GND
DCOM
DOOUT
DOGND
RONO
RONC
Digital output, PNP transistor type
30 VDC, max. 100 mA
Relay output
250 VAC / 30 VDC
V
mA
GND
Analog input circuit
common
+10V
Reference voltage
+10 VDC, max 10 mA
AI2
Not in use by default
GND
Analog input circuit common
AI1
Output frequency/speed
reference, 0…10 V
SCR
Screen
AO
GND
max. 500 ohm
Output frequency
0…20 mA
AI
1
AI
2
FlashDrop
Fieldbus adapter
DeviceNet, PROFIBUS DP,
CANopen,
Modbus RTU (RS-485)
U1
V1
W1
L1
L2
L3
3-phase power supply
U2
V2
W2
AC motor
M
3 ~
BRK+ BRK-
t°
Encoder
Brake resistor
EMC
VAR
EMC filter grounding screw
Varistor grounding screw
ROCOM
PE
10
6
6
1…10
kohm
Analog output circuit
common
8
PRO
G
RAMMABLE DI
GI
TA
L
IN
PUTS (
ABB
S
tand
ar
d
m
acr
o de
fa
ul
ts
sh
own)
Brake chopper
PROGRAMMABLE RELAY
AND DIGITAL OUTPUTS
1)
DI5 can also be used as a
frequency input.
Control panel (RJ-45)
Modbus RTU (RS-232)
Summary of Contents for ACS350 Series
Page 1: ...ACS350 User s Manual ACS350 Drives 0 37 22 kW 0 5 30 HP ...
Page 4: ......
Page 8: ...Safety 8 ...
Page 18: ...Table of contents 18 ...
Page 24: ...Hardware description 24 ...
Page 44: ...Installation checklist 44 ...
Page 56: ...Start up control with I O and ID Run 56 ...
Page 140: ...Program features 140 ...
Page 242: ...Actual signals and parameters 242 ...
Page 266: ...Fieldbus control with embedded fieldbus 266 ...
Page 284: ...Fault tracing 284 ...
Page 288: ...Maintenance and hardware diagnostics 288 ...
Page 309: ...Dimensions 309 Frame size R2 IP20 NEMA 1 3AFE68586658 A Frame size R2 IP20 NEMA 1 VAR EMC ...
Page 311: ...Dimensions 311 Frame size R3 IP20 NEMA 1 3AFE68579872 B Frame size R3 IP20 NEMA 1 VAR EMC ...
Page 313: ......