Actual signals and parameters
185
2106
DC CURR REF
Defines the DC hold current. See parameter
DC HOLD CTL.
30
0…100%
Value in percent of the motor nominal current (parameter
MOTOR NOM
CURR)
1 = 1%
2107
DC BRAKE TIME
Defines the DC brake time.
0
0.0…250.0 s
Time
1 = 0.1 s
2108
START INHIBIT
Enables the start inhibit function. Drive start is inhibited if,
- fault is reset.
- Run Enable signal activates while the start command is active. See
parameter
RUN ENABLE.
- control mode changes from local to remote.
- external control mode switches from EXT1 to EXT2 or from EXT2 to EXT1.
OFF
OFF
Disabled
0
ON
Enabled
1
2109
EMERG STOP SEL
Selects the source for the external emergency stop command.
The drive cannot be restarted before the emergency stop command is reset.
Note:
The installation must include emergency stop devices and any other
safety equipment that may be needed. Pressing STOP on the drive’s control
panel does NOT:
- generate an emergency stop of the motor
- separate the drive from dangerous potential.
NOT SEL
NOT SEL
Emergency stop function is not selected
0
DI1
Digital input DI1. 1 = stop along the emergency stop ramp. See parameter
EMER DEC TIME. 0 = emergency stop command reset.
1
DI2
See selection DI1.
2
DI3
See selection DI1.
3
DI4
See selection DI1.
4
DI5
See selection DI1.
5
DI1(INV)
Inverted digital input DI. 0 = stop along the emergency stop ramp. See
parameter
EMER DEC TIME. 1 = emergency stop command reset
-1
DI2(INV)
See selection DI1(INV).
-2
DI3(INV)
See selection DI1(INV).
-3
DI4(INV)
See selection DI1(INV).
-4
DI5(INV)
See selection DI1(INV).
-5
2110
TORQ BOOST CURR Defines the maximum supplied current during torque boost. See parameter
START FUNCTION.
100
15…300%
Value in percent
1 = 1%
2111
STOP SIGNAL DLY
Defines the stop signal delay time when parameter
STOP FUNCTION
is set to SPEED COMP.
0
0…10000 ms
Delay time
1 = 1 ms
Parameters – complete descriptions
Index Name/Selection
Description
Def, FbEq
Summary of Contents for ACS350 Series
Page 1: ...ACS350 User s Manual ACS350 Drives 0 37 22 kW 0 5 30 HP ...
Page 4: ......
Page 8: ...Safety 8 ...
Page 18: ...Table of contents 18 ...
Page 24: ...Hardware description 24 ...
Page 44: ...Installation checklist 44 ...
Page 56: ...Start up control with I O and ID Run 56 ...
Page 140: ...Program features 140 ...
Page 242: ...Actual signals and parameters 242 ...
Page 266: ...Fieldbus control with embedded fieldbus 266 ...
Page 284: ...Fault tracing 284 ...
Page 288: ...Maintenance and hardware diagnostics 288 ...
Page 309: ...Dimensions 309 Frame size R2 IP20 NEMA 1 3AFE68586658 A Frame size R2 IP20 NEMA 1 VAR EMC ...
Page 311: ...Dimensions 311 Frame size R3 IP20 NEMA 1 3AFE68579872 B Frame size R3 IP20 NEMA 1 VAR EMC ...
Page 313: ......