Actual signals and parameters
174
1607
PARAM SAVE
Saves the valid parameter values to the permanent memory.
Note:
A new parameter value of a standard macro is saved automatically
when changed from the panel but not when altered through a fieldbus
connection.
DONE
DONE
Saving completed
0
SAVE...
Saving in progress
1
1608
START ENABLE 1
Selects the source for the Start Enable 1 signal.
Note:
Functionality of the Start Enable signal is different from the Run Enable
signal.
Example:
External damper control application using Start Enable and Run
Enable. Motor can start only after the damper is fully open.
NOT SEL
NOT SEL
Start Enable signal is on.
0
DI1
External signal required through digital input DI1. 1 = Start Enable. If Start
Enable signal is switched off, the drive will not start or it coasts to stop if it is
running and alarm START ENABLE 1 MISSING is activated.
1
DI2
See selection DI1.
2
DI3
See selection DI1.
3
DI4
See selection DI1.
4
DI5
See selection DI1.
5
Parameters – complete descriptions
Index Name/Selection
Description
Def, FbEq
Drive started
Start/Stop
command
(group 10)
(1608 and 1609)
Relay energized
Relay
de-energized
Damper open
Damper
time
Damper
closing
time
Started
output status
(group 14)
Damper
status
Damper
closed
Run Enable signal
from the damper end
switch when the
damper is fully opened.
(1601)
Motor status
Acceleration
time (2202)
Deceleration
time (2203)
Start Enable
signals
Damper
closed
opening
Motor
speed
Summary of Contents for ACS350 Series
Page 1: ...ACS350 User s Manual ACS350 Drives 0 37 22 kW 0 5 30 HP ...
Page 4: ......
Page 8: ...Safety 8 ...
Page 18: ...Table of contents 18 ...
Page 24: ...Hardware description 24 ...
Page 44: ...Installation checklist 44 ...
Page 56: ...Start up control with I O and ID Run 56 ...
Page 140: ...Program features 140 ...
Page 242: ...Actual signals and parameters 242 ...
Page 266: ...Fieldbus control with embedded fieldbus 266 ...
Page 284: ...Fault tracing 284 ...
Page 288: ...Maintenance and hardware diagnostics 288 ...
Page 309: ...Dimensions 309 Frame size R2 IP20 NEMA 1 3AFE68586658 A Frame size R2 IP20 NEMA 1 VAR EMC ...
Page 311: ...Dimensions 311 Frame size R3 IP20 NEMA 1 3AFE68579872 B Frame size R3 IP20 NEMA 1 VAR EMC ...
Page 313: ......