Actual signals and parameters
147
Bit 3 = Reserved
Bit 4 = START ENABLE 1 MISSING
Bit 5 = START ENABLE 2 MISSING
Bit 6 = EMERGENCY STOP
Bit 7 = ENCODER ERROR
Bit 8 = FIRST START
Bit 9 = INPUT PHASE LOSS
Bit 10...15 = Reserved
04 FAULT HISTORY
Fault history (read-only)
0401
LAST FAULT
Code of the latest fault. See chapter
for the codes. 0 = Fault
history is clear (on panel display = NO RECORD).
1 = 1
0402
FAULT TIME 1
Day on which the latest fault occurred.
Format: Date if the real time clock is operating. / The number of days
elapsed after the power-on if the real time clock is not used, or was not
set.
1 = 1 days
0403
FAULT TIME 2
Time at which the latest fault occurred.
Format on the assistant panel: Real time (hh:mm:ss) if the real time clock
is operating. / Time elapsed after the power-on (hh:mm:ss minus the
whole days stated by signal
FAULT TIME 1) if real time clock is not
used, or was not set.
Format on the basic panel: Time elapsed after power-on in 2 second ticks
(minus the whole days stated by signal
FAULT TIME 1). 30 ticks =
60 seconds. E.g. Value 514 equals 17 minutes and 8 seconds (= 514/30).
0404
SPEED AT FLT
Motor speed in rpm at the time the latest fault occurred
1 = 1 rpm
0405
FREQ AT FLT
Frequency in Hz at the time the latest fault occurred
1 = 0.1 Hz
0406
VOLTAGE AT FLT
Intemediate circuit voltage in VDC at the time the latest fault occurred
1 = 0.1 V
0407
CURRENT AT FLT
Motor current in A at the time the latest fault occurred
1 = 0.1 A
0408
TORQUE AT FLT
Motor torque in percent of the motor nominal torque at the time the latest
fault occurred
1 = 0.1%
0409
STATUS AT FLT
Drive status in hexadecimal format at the time the latest fault occurred
0412
PREVIOUS FAULT 1
Fault code of the 2nd latest fault. See chapter
for the codes. 1 = 1
0413
PREVIOUS FAULT 2
Fault code of the 3rd latest fault. See chapter
for the codes. 1 = 1
0414
DI 1-5 AT FLT
Status of digital inputs DI1…5 at the time the latest fault occurred (binary)
Actual signals
No.
Name/Value
Description
FbEq
Summary of Contents for ACS350 Series
Page 1: ...ACS350 User s Manual ACS350 Drives 0 37 22 kW 0 5 30 HP ...
Page 4: ......
Page 8: ...Safety 8 ...
Page 18: ...Table of contents 18 ...
Page 24: ...Hardware description 24 ...
Page 44: ...Installation checklist 44 ...
Page 56: ...Start up control with I O and ID Run 56 ...
Page 140: ...Program features 140 ...
Page 242: ...Actual signals and parameters 242 ...
Page 266: ...Fieldbus control with embedded fieldbus 266 ...
Page 284: ...Fault tracing 284 ...
Page 288: ...Maintenance and hardware diagnostics 288 ...
Page 309: ...Dimensions 309 Frame size R2 IP20 NEMA 1 3AFE68586658 A Frame size R2 IP20 NEMA 1 VAR EMC ...
Page 311: ...Dimensions 311 Frame size R3 IP20 NEMA 1 3AFE68579872 B Frame size R3 IP20 NEMA 1 VAR EMC ...
Page 313: ......