384 Technical data
Ratings
Note
: When choke is not used, input current is effected by supply network and
impedance.
Use the table in
Fuses and alternate short-circuit protection
(page
) to correctly
size the input cabling as well as input fuses or MMP for branch circuit protection.
Sizing will be determined by the actual input current which is dependent on the input
line voltage and the input choke selection and rated motor current. If motor rated
current is below I
2N
, I
1N
is reduced relatively.
Type code
Input
Output
Frame
size
without choke
or reactor
with choke or
5% reactor
ACS320-
I
1N
I
1N
(480 V)
I
1N
I
1N
(480 V)
I
LD
2)
I
2N
I
2max
3)
P
N
x = E/U
1)
A
A
A
A
A
A
A
kW
hp
1-phase supply voltage 200…240 V units
(Confirm output ratings meet motor requirements)
01x-02A4-2
6.1
-
4.5
-
2.3
2.4
4.0
0.37
0.5
R0
01x-04A7-2
11.4
-
8.1
-
4.5
4.7
7.9
0.75
1
R1
01x-06A7-2
16.1
-
11.0
-
6.5
6.7
11.4
1.1
1.5
R1
01x-07A5-2
16.8
-
12.0
-
7.2
7.5
12.6
1.5
2
R2
01x-09A8-2
21.0
-
15.0
-
9.4
9.8
16.5
2.2
3
R2
3-phase supply voltage 200
…
240 V units
03x-02A6-2
4.7
-
2.6
-
2.4
2.6
4.2
0.37
0.5
R0
03x-03A9-2
6.7
-
3.9
-
3.5
3.9
6.1
0.55
0.75
R0
03x-05A2-2
8.4
-
5.2
-
4.7
5.2
8.2
0.75
1
R1
03x-07A4-2
13.0
-
7.4
-
6.7
7.4
11.7
1.1
1.5
R1
03x-08A3-2
13.2
-
8.3
-
7.5
8.3
13.1
1.5
2
R1
03x-10A8-2
15.7
-
10.8
-
9.8
10.8
17.2
2.2
3
R2
03x-14A6-2
23.9
-
14.6
-
13.3
14.6
23.3
3
3
R2
03x-19A4-2
27.3
-
19.4
-
17.6
19.4
30.8
4
5
R2
03x-26A8-2
45.0
-
26.8
-
24.4
26.8
42.7
5.5
7.5
R3
03x-34A1-2
55.0
-
34.1
-
31.0
34.1
54.3
7.5
10
R4
03x-50A8-2
76.0
-
50.8
-
46.2
50.8
80.9
11.0
15
R4
3-phase supply voltage 380
…
480 V units
03x-01A2-4
2.4
2.0
1.3
1.1
1.1
1.2
2.1
0.37
0.5
R0
03x-01A9-4
4.0
3.3
2.0
1.7
1.7
1.9
3.3
0.55
0.75
R0
03x-02A4-4
4.5
3.8
2.5
2.1
2.2
2.4
4.2
0.75
1.0
R1
03x-03A3-4
6.6
5.5
3.5
2.9
3.0
3.3
5.8
1.1
1.5
R1
03x-04A1-4
7.6
6.3
3.8
3.2
3.7
4.1
7.2
1.5
2.0
R1
03x-05A6-4
10.6
8.8
5.3
4.4
5.1
5.6
9.8
2.2
3.0
R1
03x-07A3-4
12.8
10.7
6.8
5.7
6.6
7.3
12.8
3.0
3.0
R1
03x-08A8-4
15.0
12.5
8.6
7.2
8.0
8.8
15.4
4.0
5.0
R1
03x-12A5-4
20.7
17.2
12.3
10.3
11.4
12.5
21.9
5.5
7.5
R3
Summary of Contents for ACS320 series
Page 1: ...ABB drives User s manual ACS320 drives 0 5 to 30 hp ...
Page 4: ......
Page 18: ...18 Safety ...
Page 28: ...28 Operation principle and hardware description ...
Page 56: ...56 Electrical installation ...
Page 142: ...142 Program features Connection diagram example ACS320 xx xxxx x ...
Page 282: ...282 Actual signals and parameters ...
Page 358: ...358 Fieldbus control ...
Page 376: ...376 Fault tracing ...
Page 382: ...382 Maintenance and hardware diagnostics ...
Page 407: ...Dimension drawings 407 Frame size R2 NEMA 1 Frame size R2 IP20 NEMA 1 3AUA0000051097 A ...
Page 409: ...Dimension drawings 409 Frame size R3 NEMA 1 Frame size R3 IP20 NEMA 1 3AUA0000051118 A ...
Page 411: ...Dimension drawings 411 Frame size R4 NEMA 1 Frame size R4 IP20 NEMA 1 3AUA0000051133 A ...
Page 412: ...412 Dimension drawings ...
Page 413: ...Index Numerics A B C D E F G H I K L M N O P R S T ...