Fieldbus control 329
Analog value object instance summary
The following table summarizes the Analog value objects supported:
Instance
ID
Object Name
Description
Units
Present Value
Access Type
AV0
OUTPUT
SPEED
Indicates motor speed.
RPM
R
AV1
OUTPUT
FREQ
Indicates output frequency.
Hertz
R
AV2
DC BUS VOLT Indicates DC bus voltage.
Volts
R
AV3
OUTPUT VOLT Indicates AC output voltage.
Volts
R
AV4
CURRENT
Indicates output current of the drive.
Amps
R
AV5
TORQUE
Indicates output torque of the motor as
a percentage of nominal torque.
Percent
R
AV6
POWER
Indicates output power in kW.
Kilowatts R
AV7
DRIVE TEMP
Indicates heatsink temperature.
°C
R
AV8
KWH (R)
Indicates the resettable energy usage
of the drive (reset by writing zero).
kWh
W
AV9
KWH (NR)
Indicates the cumulative energy usage
of the drive. The value cannot be reset.
kWh
R
AV10
PRC PID FBCK Process PID feedback signal.
Percent
R
AV11
PRC PID DEV
Deviation of the Process PID output
signal from its setpoint.
Percent
R
AV12
EXT PID FBCK External PID feedback signal.
Percent
R
AV13
EXT PID DEV
Deviation of External PID output signal
from its setpoint.
Percent
R
AV14
RUN TIME (R) Indicates the resettable run time of the
drive (reset by writing zero).
Hours
W
AV15
MOTOR TEMP Indicates the motor temperature as set
up in
°C
R
AV16
INPUT REF 1
Sets the input Reference 1 (drive must
be configured for BACnet control).
Percent
C
AV17
INPUT REF 2
Sets the input Reference 2 (drive must
be configured for BACnet control).
Percent
C
AV18
LAST FLT
Indicates most recent fault in the fault
log.
None
R
AV19
PREV FLT 1
Indicates previous fault in the fault log. None
R
AV20
PREV FLT 2
Indicates the oldest fault in the fault log. None
R
AV21
AO 1 ACT
Indicates output level of Analog
Output 1.
Milliamps R
AV23
ACCEL1 TIME Sets Ramp1 acceleration time.
Seconds W
AV24
DECEL1 TIME Sets Ramp1 deceleration time.
Seconds W
AV25
MBOX PARAM Sets the parameter to be used by the
mailbox function. See BV15 and BV16.
None
W
AV26
MBOX DATA
Sets (W) or indicates (R) as the data
value of mailbox function (see BV15
and BV16).
None
W
Summary of Contents for ACS320 series
Page 1: ...ABB drives User s manual ACS320 drives 0 5 to 30 hp ...
Page 4: ......
Page 18: ...18 Safety ...
Page 28: ...28 Operation principle and hardware description ...
Page 56: ...56 Electrical installation ...
Page 142: ...142 Program features Connection diagram example ACS320 xx xxxx x ...
Page 282: ...282 Actual signals and parameters ...
Page 358: ...358 Fieldbus control ...
Page 376: ...376 Fault tracing ...
Page 382: ...382 Maintenance and hardware diagnostics ...
Page 407: ...Dimension drawings 407 Frame size R2 NEMA 1 Frame size R2 IP20 NEMA 1 3AUA0000051097 A ...
Page 409: ...Dimension drawings 409 Frame size R3 NEMA 1 Frame size R3 IP20 NEMA 1 3AUA0000051118 A ...
Page 411: ...Dimension drawings 411 Frame size R4 NEMA 1 Frame size R4 IP20 NEMA 1 3AUA0000051133 A ...
Page 412: ...412 Dimension drawings ...
Page 413: ...Index Numerics A B C D E F G H I K L M N O P R S T ...