328 Fieldbus control
*Object instance applies for US regional variant only.
Note:
For Present Value Access Types, R = Read-only, W = Writeable,
C = Commandable. Commandable values support priority arrays & relinquish
defaults.
Analog input object instance summary
The following table summarizes the Analog input objects supported:
Note:
For Present Value Access Types, R = Read-only, W = Writeable,
C = Commandable. Commandable values support priority arrays & relinquish
defaults.
Analog output object instance summary
The following table summarizes the Analog output objects supported:
Note:
For Present Value Access Types, R = Read-only, W = Writeable,
C = Commandable. Commandable values support priority arrays & relinquish
defaults.
BV22*
HEATING CMD
Command to automatically
assert Motor Heating DC
current injection, when drive
is stopped (drive must be
configured for BACnet
control).
In this mode, “DISABLE”
turns off the ongoing Motor
Heating operation
immediately (after the drive
has received the command).
ENABLE/DISABLE C
BV23*
HEATING STS
Indicates the status of Motor
Heating DC current injection
(drive must be configured
for BACnet control).
“ON” means there is actual
heating current flowing in
the motor circuit.
ON/OFF
R
Instance
ID
Object Name
Description
Units
Present Value
Access Type
AI0
ANALOG INPUT
1
Indicates the input level of Analog
Input 1.
Percent R
AI1
ANALOG INPUT
2
Indicates the input level of Analog
Input 2.
Percent R
Instance
ID
Object Name
Description
Units
Present Value
Access Type
AO0
AO 1
COMMAND
Controls Analog Output 1 (drive must
be configured for BACnet control).
Percent C
Instance
ID
Object Name
Description
Active/Inactive
Text
Present Value
Access Type
Summary of Contents for ACS320 series
Page 1: ...ABB drives User s manual ACS320 drives 0 5 to 30 hp ...
Page 4: ......
Page 18: ...18 Safety ...
Page 28: ...28 Operation principle and hardware description ...
Page 56: ...56 Electrical installation ...
Page 142: ...142 Program features Connection diagram example ACS320 xx xxxx x ...
Page 282: ...282 Actual signals and parameters ...
Page 358: ...358 Fieldbus control ...
Page 376: ...376 Fault tracing ...
Page 382: ...382 Maintenance and hardware diagnostics ...
Page 407: ...Dimension drawings 407 Frame size R2 NEMA 1 Frame size R2 IP20 NEMA 1 3AUA0000051097 A ...
Page 409: ...Dimension drawings 409 Frame size R3 NEMA 1 Frame size R3 IP20 NEMA 1 3AUA0000051118 A ...
Page 411: ...Dimension drawings 411 Frame size R4 NEMA 1 Frame size R4 IP20 NEMA 1 3AUA0000051133 A ...
Page 412: ...412 Dimension drawings ...
Page 413: ...Index Numerics A B C D E F G H I K L M N O P R S T ...