Fieldbus control 319
a.Points not listed are not used in this application.
b.A single value in a column means that the value is the same in English units and in SI units.
c.Point numbers that appear in brackets { } may be unbundled at the field panel.
Detailed point descriptions
{94} LDO RESET FAULT
NO
-
1
0
RESET
NO
{95} LAO MBOX PARAM
-
-
1
0
-
-
{96} LAO MBOX DATA
-
-
1
0
-
-
{97} LDO MBOX READ
DONE
-
1
0
READ
DONE
{98} LDO MBOX WRITE
DONE
-
1
0
WRITE
DONE
{99} LAO ERROR
STATUS
-
-
1
0
-
-
FLN Detailed Point Descriptions
Point
Description
Drive
Parameter
1
CTRL
ADDRESS
The FLN address of the drive. It can be set by FLN and
by the panel.
5302
2
APPLICATION
The Application ID for FLN on the ACS320. This ID is
assigned by Siemens for each unique application. It
correlates directly to a particular point list approved at
the time of release. Therefore, this point list shall remain
fixed once approval is granted. Any changes to the point
list shall require a new Application ID and re-approval by
Siemens. The Application ID assigned to ACS320 is
2934.
3
FREQ OUTPUT The output frequency applied to the motor, in Hertz.
0103
4
PCT OUTPUT
The ratio of output frequency or speed to the
corresponding maximum rating, depending on control
mode.
For scalar mode, it is the ratio of Output Frequency
(parameter 0103) to Maximum Frequency (parameter
2008).
None. This
ratio is
calculated
by the FLN
application.
5
SPEED
The calculated speed of the motor, in RPM.
0102
6
CURRENT
The measured output current.
0104
7
TORQUE
The calculated output torque of the motor as a
percentage of nominal torque.
0105
8
POWER
The measured output power in KW. The FLN point
definition also supports horsepower by selecting English
units.
0106
9
DRIVE TEMP
The measured heatsink temperature, in
°
C. The FLN
point definition also supports
°
F by selecting English
units.
0110
10
DRIVE KWH
The drive's cumulative power consumption in kilowatt-
hours. This value may be reset by commanding FLN
point 49, RESET KWH.
0115
FLN Point Database
Point
Subpoint Name
Factory
Default
Engr.
Units
Slope
Intercept
On Text
Off Text
#
Type
(SI Units)
Summary of Contents for ACS320 series
Page 1: ...ABB drives User s manual ACS320 drives 0 5 to 30 hp ...
Page 4: ......
Page 18: ...18 Safety ...
Page 28: ...28 Operation principle and hardware description ...
Page 56: ...56 Electrical installation ...
Page 142: ...142 Program features Connection diagram example ACS320 xx xxxx x ...
Page 282: ...282 Actual signals and parameters ...
Page 358: ...358 Fieldbus control ...
Page 376: ...376 Fault tracing ...
Page 382: ...382 Maintenance and hardware diagnostics ...
Page 407: ...Dimension drawings 407 Frame size R2 NEMA 1 Frame size R2 IP20 NEMA 1 3AUA0000051097 A ...
Page 409: ...Dimension drawings 409 Frame size R3 NEMA 1 Frame size R3 IP20 NEMA 1 3AUA0000051118 A ...
Page 411: ...Dimension drawings 411 Frame size R4 NEMA 1 Frame size R4 IP20 NEMA 1 3AUA0000051133 A ...
Page 412: ...412 Dimension drawings ...
Page 413: ...Index Numerics A B C D E F G H I K L M N O P R S T ...