Fieldbus control 295
Relay output control
Using the fieldbus for relay output control requires:
• Drive parameter values set as defined below.
• Fieldbus controller supplied reference word(s) in the appropriate location. (The
location is defined by the Protocol Reference, which is protocol dependent.)
1. More than 1 relay requires the addition of a relay extension module.
For example:
To control relays 1 and 2 using serial communication:
Set parameters
and
= 35 (
COMM
).
Then, for example using N2:
• To turn Relay 1 On: Force object B07 to On.
• To turn Relay 2 On: Force object B08 to On.
• To turn both Relay 1 and 2 On: Force objects B07 and B08 On.
Note:
Relay status feedback occurs without configuration as defined below.
Drive Parameter
Value
Setting
Protocol Reference
Modbus
N2
FLN BACnet
abb drv
dcu
profile
1401
RELAY
OUTPUT
1
35
(COMM)
Relay Output 1
controlled by fieldbus.
40134 bit 0 or
00033
BO7
40
BO0
1402
1
RELAY
OUTPUT
2
35
(COMM)
Relay Output 2
controlled by fieldbus.
40134 bit 2 or
00034
BO8
41
BO1
1403
1
RELAY
OUTPUT
3
35
(COMM)
Relay Output 3
controlled by fieldbus.
40134 bit 3 or
00035
BO9
42
BO2
1410
1
RELAY
OUTPUT
4
35
(COMM)
Relay Output 4
controlled by fieldbus.
40134 bit 4 or
00036
BO10 43
BO3
Drive
Parameter
Value
Setting
Protocol Reference
Modbus
N2
FLN
BACnet
abb drv
dcu profile
0162 RO
STATUS
Relay status.
40122
0122
BI4…
BI6
76…
78
BI0…
BI2
0173 RO 2-4
STATUS
Relay 2-4
status.
40123
0123
BI7
79
BI3
Summary of Contents for ACS320 series
Page 1: ...ABB drives User s manual ACS320 drives 0 5 to 30 hp ...
Page 4: ......
Page 18: ...18 Safety ...
Page 28: ...28 Operation principle and hardware description ...
Page 56: ...56 Electrical installation ...
Page 142: ...142 Program features Connection diagram example ACS320 xx xxxx x ...
Page 282: ...282 Actual signals and parameters ...
Page 358: ...358 Fieldbus control ...
Page 376: ...376 Fault tracing ...
Page 382: ...382 Maintenance and hardware diagnostics ...
Page 407: ...Dimension drawings 407 Frame size R2 NEMA 1 Frame size R2 IP20 NEMA 1 3AUA0000051097 A ...
Page 409: ...Dimension drawings 409 Frame size R3 NEMA 1 Frame size R3 IP20 NEMA 1 3AUA0000051118 A ...
Page 411: ...Dimension drawings 411 Frame size R4 NEMA 1 Frame size R4 IP20 NEMA 1 3AUA0000051133 A ...
Page 412: ...412 Dimension drawings ...
Page 413: ...Index Numerics A B C D E F G H I K L M N O P R S T ...