Actual signals and parameters 255
Group 52: Panel comm
This group defines the communication settings for the control panel port on the drive.
Normally, when using the supplied control panel, there is no need to change settings
in this group.
In this group, parameter modifications take effect on the next power-up.
Group 52: Panel comm
Code
Description
Range
Resolution
Default
S
5201
STATION ID
1…247
1
1
Defines the address of the drive. Two units with the same address are not allowed on-
line.
• Range: 1…247
5202
BAUD RATE
9.6 … 115.2 kbits/s
-
9.6 kbits/s
Defines the transfer rate of the link.
9.6
19.2
38.4
57.6
115.2
5203
PARITY
0…3
1
0
Defines the use of parity and stop bit(s). The same setting must be used in all on-line
stations.
0 = 8N1 – 8 data bits, no parity, one stop bit.
1 = 8N2 – 8 data bits, no parity, two stop bits.
2 = 8E1 – 8 data bits, even parity indication bit, one stop bit.
3 = 8O1 – 8 data bits, odd parity indication bit, one stop bit.
5204
OK MESSAGES
0…65535
1
-
Number of valid messages received by the drive. During normal operation, this number
increases constantly.
5205
PARITY ERRORS
0…65535
1
-
Number of characters with a parity error received from the Modbus link. If the number
is high, check that the parity settings of the devices connected on the bus are the
same.
Note:
High electromagnetic noise levels generate errors.
5206
FRAME ERRORS
0…65535
1
-
Number of characters with a framing error received by the Modbus link. If the number
is high, check that the communication speed settings of the devices connected on the
bus are the same.
Note:
High electromagnetic noise levels generate errors.
5207
BUFFER
OVERRUNS
0…65535
1
-
Number of characters which overflow the buffer, in other words, number of characters
which exceed the maximum message length, 128 bytes.
Summary of Contents for ACS320 series
Page 1: ...ABB drives User s manual ACS320 drives 0 5 to 30 hp ...
Page 4: ......
Page 18: ...18 Safety ...
Page 28: ...28 Operation principle and hardware description ...
Page 56: ...56 Electrical installation ...
Page 142: ...142 Program features Connection diagram example ACS320 xx xxxx x ...
Page 282: ...282 Actual signals and parameters ...
Page 358: ...358 Fieldbus control ...
Page 376: ...376 Fault tracing ...
Page 382: ...382 Maintenance and hardware diagnostics ...
Page 407: ...Dimension drawings 407 Frame size R2 NEMA 1 Frame size R2 IP20 NEMA 1 3AUA0000051097 A ...
Page 409: ...Dimension drawings 409 Frame size R3 NEMA 1 Frame size R3 IP20 NEMA 1 3AUA0000051118 A ...
Page 411: ...Dimension drawings 411 Frame size R4 NEMA 1 Frame size R4 IP20 NEMA 1 3AUA0000051133 A ...
Page 412: ...412 Dimension drawings ...
Page 413: ...Index Numerics A B C D E F G H I K L M N O P R S T ...