Actual signals and parameters 235
4015
FBK MULTIPLIER
-32.768…32.767 0.001
0
Defines an extra multiplier for the PID FBK value defined by parameter
• Used mainly in applications where the flow is calculated from the pressure
difference.
0 = NOT SELECTED.
-32.768…32.767 = Multiplier applied to the signal defined by parameter
.
Example:
4016
ACT1 INPUT
1…8
1
2
Defines the source for actual value 1 (ACT1).
1 = AI 1 – Uses analog input 1 for ACT1.
2 = AI 2 – Uses analog input 2 for ACT1.
3 = CURRENT – Uses current for ACT1, scaled so:
• Min ACT1 = 0 current
• Max ACT1 = 2 x nominal current
4 = TORQUE – Uses torque for ACT1, scaled so:
• Min ACT1= -2 x nominal torque
• Max ACT1 = 2 x nominal torque
5 = POWER – Uses power for ACT1, scaled so:
• Min ACT1 = -2 x nominal power
• Max ACT1 = 2 x nominal power
6 = COMM ACT 1 – Uses value of signal
for ACT1.
7 = COMM ACT 2 – Uses value of signal
for ACT1.
8 = FREQ INPUT
4017
ACT2 INPUT
1…8
1
2
Defines the source for actual value 2 (ACT2).
1 = AI 1 – Uses analog input 1 for ACT2.
2 = AI 2 – Uses analog input 2 for ACT2.
3 = CURRENT – Uses current for ACT2, scaled so:
• Min ACT2 = 0 current
• Max ACT2 = 2 x nominal current
4 = TORQUE – Uses torque for ACT2, scaled so:
• Min ACT2 = -2 x nominal torque
• Max ACT2 = 2 x nominal torque
5 = POWER – Uses power for ACT2, scaled so:
• Min ACT2 = -2 x nominal power
• Max ACT2 = 2 x nominal power
6 = COMM ACT 1 – Uses value of signal
for ACT2.
7 = COMM ACT 2 – Uses value of signal
for ACT2.
8 = FREQ INPUT – Frequency input.
Group 40: Process PID set 1
Code
Description
Range
Resolution
Default
S
FBK
Multiplier
A
1
A
2
–
×
=
Summary of Contents for ACS320 series
Page 1: ...ABB drives User s manual ACS320 drives 0 5 to 30 hp ...
Page 4: ......
Page 18: ...18 Safety ...
Page 28: ...28 Operation principle and hardware description ...
Page 56: ...56 Electrical installation ...
Page 142: ...142 Program features Connection diagram example ACS320 xx xxxx x ...
Page 282: ...282 Actual signals and parameters ...
Page 358: ...358 Fieldbus control ...
Page 376: ...376 Fault tracing ...
Page 382: ...382 Maintenance and hardware diagnostics ...
Page 407: ...Dimension drawings 407 Frame size R2 NEMA 1 Frame size R2 IP20 NEMA 1 3AUA0000051097 A ...
Page 409: ...Dimension drawings 409 Frame size R3 NEMA 1 Frame size R3 IP20 NEMA 1 3AUA0000051118 A ...
Page 411: ...Dimension drawings 411 Frame size R4 NEMA 1 Frame size R4 IP20 NEMA 1 3AUA0000051133 A ...
Page 412: ...412 Dimension drawings ...
Page 413: ...Index Numerics A B C D E F G H I K L M N O P R S T ...