Actual signals and parameters 181
1605
USER PAR SET CHG
-5…5
1
0
Defines control for changing the user parameter set.
• See parameter
.
• The drive must be stopped to change User parameter sets.
• During a change, the drive will not start.
Note:
Always save the User parameter set after changing any parameter settings, or
performing a motor identification.
• Whenever the power is cycled, or parameter
is changed, the
drive loads the last settings saved. Any unsaved changes to a user parameter set
are lost.
Note:
The value of this parameter (1605) is not included in the User parameter sets,
and does not change if User parameter sets change.
Note:
You can use a relay output to supervise the selection of User parameter set 2.
• See parameter 1401.
0 = NOT SEL – Defines the control panel (using parameter
) as
the only control for changing User parameter sets.
1 = DI1 – Defines digital input 1 as a control for changing User parameter sets.
• The drive loads User parameter set 1 on the falling edge of the digital input.
• The drive loads User parameter set 2 on the rising edge of the digital input.
• The User parameter set changes only when the drive is stopped.
2…5 = DI2…DI5 – Defines digital input DI2…DI5 as a control for changing User
parameter sets.
• See DI1 above.
-1 = DI1(INV) – Defines an inverted digital input 1 as a control for changing User
parameter sets.
• The drive loads User parameter set 1 on the rising edge of the digital input.
• The drive loads User parameter set2 on the falling edge of the digital input.
• The User parameter set changes only when the drive is stopped.
-2…-5 = DI2(INV)…DI5(INV) – Defines an inverted digital input DI2…DI5 as a control
for changing User parameter sets.
• See DI1(INV) above.
Group 16: System controls
Code
Description
Range
Resolution
Default
S
Summary of Contents for ACS320 series
Page 1: ...ABB drives User s manual ACS320 drives 0 5 to 30 hp ...
Page 4: ......
Page 18: ...18 Safety ...
Page 28: ...28 Operation principle and hardware description ...
Page 56: ...56 Electrical installation ...
Page 142: ...142 Program features Connection diagram example ACS320 xx xxxx x ...
Page 282: ...282 Actual signals and parameters ...
Page 358: ...358 Fieldbus control ...
Page 376: ...376 Fault tracing ...
Page 382: ...382 Maintenance and hardware diagnostics ...
Page 407: ...Dimension drawings 407 Frame size R2 NEMA 1 Frame size R2 IP20 NEMA 1 3AUA0000051097 A ...
Page 409: ...Dimension drawings 409 Frame size R3 NEMA 1 Frame size R3 IP20 NEMA 1 3AUA0000051118 A ...
Page 411: ...Dimension drawings 411 Frame size R4 NEMA 1 Frame size R4 IP20 NEMA 1 3AUA0000051133 A ...
Page 412: ...412 Dimension drawings ...
Page 413: ...Index Numerics A B C D E F G H I K L M N O P R S T ...