150 Actual signals and parameters
Group 01: Operating data
This group contains drive operating data, including actual signals. The drive sets the
values for actual signals, based on measurements or calculations. You cannot set
these values.
Group 01: Operating data
Code
Description
Range
Resolution
Default
S
0101
SPEED & DIR
-30000...30000
1 rpm
-
The calculated speed of the motor (rpm) & motor direction.
0102
SPEED
0 … 30000 rpm
1 rpm
-
The calculated speed of the motor (rpm).
0103
OUTPUT FREQ
0.0 … 500.0 Hz
1Hz
-
The frequency (Hz) applied to the motor. (Also shown by default in OUTPUT display.)
0104
CURRENT
0.0 … 1.5*I
2N
0.1 A
-
The motor current, as measured by the drive. (Also shown by default in OUTPUT
display.)
0105
TORQUE
-200% … 200%
0.1%
-
Output torque. Calculated value of torque on motor shaft in % of motor nominal torque.
0106
POWER
-1.5 … 1.5*P
N
0.1 kW
-
The measured motor power in kW.
0107
DC BUS VOLTAGE
0 V … 2.5*V
dN
1 V
-
The DC bus voltage in VDC, as measured by the drive.
0109
OUTPUT VOLTAGE
0 V … 2.0*V
dN
1 V
-
The voltage applied to the motor.
0110
DRIVE TEMP
0
°
C … 150
°
C
1
°
C
-
The temperature of the drive power transistors in Celsius.
0111
EXTERNAL REF 1
0 … 500 Hz
0.1 Hz
-
External reference, REF1or Hz.
0112
EXTERNAL REF 2
0% … 100%
(torque: 0% … 600%)
0.1%
-
External reference, REF2, in %
0113
CTRL LOCATION
0 … 2
1
-
Active control location. Alternatives are:
0 = HAND
1 = EXT1
2 = EXT2
0114
RUN TIME (R)
0 … 10000 h
1 h
0 h
The drive’s accumulated running time in hours (h).
• Can be
reset
by pressing UP and DOWN buttons simultaneously when in
parameter set mode.
Summary of Contents for ACS320 series
Page 1: ...ABB drives User s manual ACS320 drives 0 5 to 30 hp ...
Page 4: ......
Page 18: ...18 Safety ...
Page 28: ...28 Operation principle and hardware description ...
Page 56: ...56 Electrical installation ...
Page 142: ...142 Program features Connection diagram example ACS320 xx xxxx x ...
Page 282: ...282 Actual signals and parameters ...
Page 358: ...358 Fieldbus control ...
Page 376: ...376 Fault tracing ...
Page 382: ...382 Maintenance and hardware diagnostics ...
Page 407: ...Dimension drawings 407 Frame size R2 NEMA 1 Frame size R2 IP20 NEMA 1 3AUA0000051097 A ...
Page 409: ...Dimension drawings 409 Frame size R3 NEMA 1 Frame size R3 IP20 NEMA 1 3AUA0000051118 A ...
Page 411: ...Dimension drawings 411 Frame size R4 NEMA 1 Frame size R4 IP20 NEMA 1 3AUA0000051133 A ...
Page 412: ...412 Dimension drawings ...
Page 413: ...Index Numerics A B C D E F G H I K L M N O P R S T ...