342 Technical data
Size of copper conductor in cablings
Cable dimensioning for rated currents (I
1N
) is shown in the table below.
5)
Requires the use of S1-M3-25 line side feeder terminal with the manual motor protector to meet type E self
protection class.
6)
For all drives, the enclosure must be sized to accommodate the specific thermal considerations of the
applications as well as provide free space for cooling. See section,
.
For UL only: The minimum enclosure volume is specified in the UL listing for drive frames R0 and R1 when
applied with the ABB type E MMP shown in the table. ACS310 drives are intended to be mounted in an
enclosure unless a NEMA 1 kit is added.
For ratings marked with *-* the minimum size is determined by the thermal requirements of the drive and any
other equipment in the enclosure.
Type
Size of copper conductor in cablings
ACS310-
Supply
(U1, V1, W1)
Motor
(U2, V2, W2)
PE
x = E/U
1)
mm
2
AWG
mm
2
AWG
mm
2
AWG
1-phase
U
N
= 200…240 V
(200, 208, 220, 230, 240 V)
01x-02A4-2
2.5
14
0.75
18
2.5
14
01x-04A7-2
2.5
14
0.75
18
2.5
14
01x-06A7-2
2.5
10
1.5
14
2.5
10
01x-07A5-2
2.5
10
1.5
14
2.5
10
01x-09A8-2
6
10
2.5
12
6
10
3-phase
U
N
= 200
…
240 V
(200, 208, 220, 230, 240 V)
03x-02A6-2
2.5
14
1.5
14
2.5
14
03x-03A9-2
2.5
14
1.5
14
2.5
14
03x-05A2-2
2.5
14
1.5
14
2.5
14
03x-07A4-2
2.5
12
1.5
14
2.5
12
03x-08A3-2
2.5
12
1.5
14
2.5
12
03x-10A8-2
2.5
12
2.5
12
2.5
12
03x-14A6-2
6.0
10
6
10
6.0
10
03x-19A4-2
6.0
10
6
10
6.0
10
03x-26A8-2
10.0
8
10
8
10.0
8
03x-34A1-2
16.0
6
16
6
16.0
6
03x-50A8-2
25.0
2
25
2
16.0
4
3-phase
U
N
= 380
…
480 V
(380, 400, 415, 440, 460, 480 V)
03x-01A3-4
2.5
14
1.5
14
2.5
14
03x-02A1-4
2.5
14
1.5
14
2.5
14
03x-02A6-4
2.5
14
1.5
14
2.5
14
03x-03A6-4
2.5
12
1.5
14
2.5
12
03x-04A5-4
2.5
12
1.5
14
2.5
12
03x-06A2-4
2.5
12
1.5
14
2.5
12
03x-08A0-4
2.5
12
1.5
14
2.5
12
03x-09A7-4
2.5
12
2.5
12
2.5
12
03x-13A8-4
6.0
10
6
10
6.0
10
03x-17A2-4
6.0
8
6
8
6.0
8
03x-25A4-4
10.0
8
10
8
10.0
8
Aotewell Ltd
www.aotewell.com
Industry Automation
HongKong|UK|China