Actual signals and parameters 205
2202 ACCELER
TIME 1
Defines the acceleration time 1, that is, the time required for
the speed to change from zero to the speed defined by
.
• If the speed reference increases faster than the set
acceleration rate, the motor speed follows the
acceleration rate.
• If the speed reference increases slower than the set
acceleration rate, the motor speed follows the reference
signal.
• If the acceleration time is set too short, the drive
automatically prolongs the acceleration in order not to
exceed the drive operating limits.
Actual acceleration time depends on parameter
setting.
5.0 s
0.0…1800.0 s
Time
1 = 0.1 s
2203 DECELER
TIME 1
Defines the deceleration time 1, that is, the time required for
the speed to change from the value defined by parameter
to zero.
• If the speed reference decreases slower than the set
deceleration rate, the motor speed follows the reference
signal.
• If the reference changes faster than the set deceleration
rate, the motor speed follows the deceleration rate.
• If the deceleration time is set too short, the drive
automatically prolongs the deceleration in order not to
exceed drive operating limits.
If a short deceleration time is needed for a high inertia
application, note that the ACS310 cannot be equipped with
a brake resistor.
Actual deceleration time depends on parameter
setting.
5.0 s
0.0…1800.0 s
Time
1 = 0.1 s