Program features 129
Diagnostics
Power loss ride-through
If the incoming supply voltage is cut off, the drive continues to operate by utilizing the
kinetic energy of the rotating motor. The drive is fully operational as long as the motor
rotates and generates energy to the drive. The drive can continue the operation after
the break if the main contactor remained closed.
Settings
Parameter
Group
Selection of an actual signals to be displayed on the
control panel
Actual signal
Additional information
…
Lists of actual signals
Parameter
Additional information
130
260
390
520
1.6
4.8
8
11.2
14.4
t
(s)
U
DC
f
out
T
M
U
DC
= Intermediate circuit voltage of the drive,
f
out
= Output frequency of the drive,
T
M
= Motor torque
Loss of supply voltage at nominal load (
f
out
= 40 Hz). The intermediate circuit DC voltage drops
to the minimum limit. The controller keeps the voltage steady as long as the input power is
switched off. The drive runs the motor in generator mode. The motor speed falls but the drive is
operational as long as the motor has enough kinetic energy.