min. 300 mm (12 in)
min. 300 mm (12 in)
min. 500 mm (20 in)
min. 500 mm (20 in)
min. 200 mm (8 in)
90°
1
2
4
4
3
2
1
3
2
3
Motor cable
1
Input power cable
2
Control cable
3
Brake resistor or chopper cable (if any)
4
■
General guidelines – North America
Make sure that the installation is in accordance with national and local codes. Obey
these general guidelines:
•
Use separate conduits for the input power, motor, brake resistor (optional),
and control cabling.
•
Use separate conduit for each motor cabling.
The following figure illustrates the cable routing guidelines with an example drive.