Start-up including validation test
To ensure the safe operation of a safety function, validation is required. The final
assembler of the machine must validate the function by performing a validation
test. The test must be performed
1.
at initial start-up of the safety function
2.
after any changes related to the safety function (circuit boards, wiring,
components, settings, replacement of inverter module, etc.)
3.
after any maintenance work related to the safety function
4. after a drive firmware update
5. at the proof test of the safety function.
■
Competence
The validation test of the safety function must be carried out by a competent
person with adequate expertise and knowledge of the safety function as well as
functional safety, as required by IEC 61508-1 clause 6. The test procedures and
report must be documented and signed by this person.
■
Validation test reports
Signed validation test reports must be stored in the logbook of the machine. The
report shall include documentation of start-up activities and test results, references
to failure reports and resolution of failures. Any new validation tests performed
due to changes or maintenance shall be logged into the logbook.
■
Validation test procedure
After wiring the Safe torque off function, validate its operation as follows.
Action
WARNING!
Obey the safety instructions. If you ignore them, injury or death, or damage to
the equipment can occur.
Make sure that the motor can be run and stopped freely during start-up.
Stop the drive (if running), switch the input power off and isolate the drive from the
power line using a disconnector.
Check the STO circuit connections against the wiring diagram.
Close the disconnector and switch the power on.
152 The Safe torque off function
Summary of Contents for ACS180
Page 1: ...ABB MACHINERY DRIVES ACS180 drives Hardware manual...
Page 2: ......
Page 4: ......
Page 12: ...12...
Page 36: ...36...
Page 41: ...4 Tighten the mounting screws Mechanical installation 41...
Page 58: ...58...
Page 76: ...76...
Page 90: ...90...
Page 130: ...Frame R0 130 Dimension drawings...
Page 131: ...Frame R1 Dimension drawings 131...
Page 133: ...Frame R3 Dimension drawings 133...
Page 134: ...Frame R4 134 Dimension drawings...
Page 142: ...142...
Page 162: ...Declarations of conformity 162 The Safe torque off function...
Page 163: ...The Safe torque off function 163...
Page 164: ...164 The Safe torque off function...
Page 165: ...The Safe torque off function 165...
Page 166: ...166...