290 Parameters
Defines the stator resistance
R
S
of the motor model.
With a star-connected motor,
R
S
is the resistance of one
winding. With a delta-connected motor,
R
S
is one-third of
the resistance of one winding.
0.00000 p.u.
0.00000…0.50000
p.u.
Stator resistance in per unit.
-
Defines the rotor resistance
R
R
of the motor model.
Note:
This parameter is valid only for asynchronous
motors.
0.00000 p.u.
0.00000…0.50000
p.u.
Rotor resistance in per unit.
-
Defines the main inductance
L
M
of the motor model.
Note:
This parameter is valid only for asynchronous
motors.
0.00000 p.u.
0.00000… 10.00000
p.u.
Main inductance in per unit.
-
Defines the leakage inductance
L
S
.
Note:
This parameter is valid only for asynchronous
motors.
0.00000 p.u.
0.00000…1.00000
p.u.
Leakage inductance in per unit.
-
Defines the direct axis (synchronous) inductance.
Note:
This parameter is valid only for permanent magnet
motors.
0.00000 p.u.
0.00000 … 10.00000
p.u
Direct axis inductance in per unit.
-
Defines the quadrature axis (synchronous) inductance.
Note:
This parameter is valid only for permanent magnet
motors.
0.00000 p.u.
0.00000 … 10.00000
p.u
Quadrature axis inductance in per unit.
-
Defines the permanent magnet flux.
Note:
This parameter is valid only for permanent magnet
motors.
0.00000 p.u.
0.00000 … 2.00000
p.u
Permanent magnet flux in per unit.
-
Defines the stator resistance
R
S
of the motor model.
0.00000 ohm
0.00000…
100.00000 ohm
Stator resistance.
-
Defines the rotor resistance
R
R
of the motor model.
Note:
This parameter is valid only for asynchronous
motors.
0.00000 ohm
0.00000…
100.00000 ohm
Rotor resistance.
-
Defines the main inductance
L
M
of the motor model.
Note:
This parameter is valid only for asynchronous
motors.
0.00 mH
0.00…100000.00 mH
Main inductance.
1 = 10000
mH
No.
Name/Value
Description
Default
FbEq 16