142 Parameters
Enables/disables local control (start and stop buttons on
the control panel, and the local controls on the PC tool).
WARNING!
Before disabling local control, ensure
that the control panel is not needed for stopping
the drive.
No
Local control enabled.
0
Yes
Local control disabled.
1
20
Start/stop/direction and run/start/jog enable signal source
selection; positive/negative reference enable signal
source selection.
For information on control locations, see section
and external control locations
).
Selects the source of start, stop and direction commands
for external control location 1 (EXT1).
See also parameters
. See parameter
for the determination of the actual direction.
Not selected
No start or stop command sources selected.
0
In1 Start
The source of the start and stop commands is selected by
parameter
. The state transitions of
the source bits are interpreted as follows:
1
In1 Start; In2 Dir
The source selected by
is the start
signal; the source selected by
determines the direction. The state transitions of the
source bits are interpreted as follows:
2
In1 Start fwd; In2 Start
rev
The source selected by
is the
forward start signal; the source selected by
is the reverse start signal. The state transitions of
the source bits are interpreted as follows:
3
No.
Name/Value
Description
Default
FbEq 16
State of source 1
(
Command
0 -> 1 (
)
1 (
Start
0
Stop
State of source 1
(
)
State of source 2
Command
0
Any
Stop
0 -> 1 (
)
1 (
0
Start forward
1
Start reverse
State of source 1
(
State of source 2
(
Command
0
0
Stop
0 -> 1 (
)
0
Start forward
0
0 -> 1 (
1 (
Start reverse
1
1
Stop
ACS180 FW.book Page 142 Tuesday, March 9, 2021 2:25 PM