11 PREVENTIVE AND CORRECTIVE MAINTENANCE
3BHS206977 E01 REV H
ACS1000I AIR-COOLED
USER MANUAL
154/174
11.3
Alarm / fault indications
11.3.1
Messages
When a failure occurs in the drive or in the equipment monitored by the drive (eg, main circuit
breaker, transformer, cooling system), the CDP control panel displays a corresponding alarm
or fault message.
The message can be saved and viewed in the fault history of the drive when a PC with the
DriveWindow and DriveDebug is connected to the drive. The fault logger can also be called up
on the CDP control panel.
11.3.2
Error message levels
Two error message levels are used in the drive:
-
Alarm
: Does not shut down the drive. If the condition causing the alarm is not corrected, a
persisting alarm can lead to a fault. An alarm cannot be reset manually. The alarm message
is deleted from the display as soon as the alarm condition has been corrected.
Note:
An exception is when an alarm of the cooling system (eg, FanDiffPres, AirFiltSupv) is
not reset automatically. To reset the alarm, set parameter 41.04 FanAlarmReset to RESET.
-
Fault
: A fault shuts down the drive. The type of shutdown depends on the origin of the fault.
Depending on the type of fault, the drive opens the main circuit breaker (MCB) or keeps it
closed. A fault condition must be corrected and the fault be manually reset before the drive
can be started again.
11.3.2.1
Alarm / fault messages
If an alarm or a fault occurs, a specific message is saved in the fault buffer of the drive.
Information on the 64 most recent fault and alarm events are saved.
11.3.3
Fault handling
The faults are entered into the fault logger as they occur and are numbered:
- The last fault entered always has number 1 assigned to it.
- The first fault always has the highest number in the fault buffer.
Date and time stamps facilitate fault tracing, especially when a fault leads to several
subsequent faults.
1 L ->
600.0 rpm
ACS1000
*** FAULT ***
MCB CloseControl
Summary of Contents for ACS1000i air-cooled
Page 1: ... MEDIUM VOLTAGE AC DRIVES ACS1000i air cooled User manual ...
Page 3: ...Contents ACS1000i air cooled User manual ...
Page 5: ... 01 About this manual 01 5 16 ...
Page 16: ......
Page 17: ... 02 Important safety information 02 17 28 ...
Page 28: ......
Page 29: ... 03 Power electronics and cabinet features03 29 56 ...
Page 57: ... 04 Control system 04 57 70 ...
Page 71: ... 05 Transportation storage and disposal05 71 78 ...
Page 78: ......
Page 79: ... 06 Mechanical installation 06 79 88 ...
Page 88: ......
Page 89: ... 07 Electrical installation07 89 104 ...
Page 105: ... 08 Commissioning 08 105 110 ...
Page 110: ......
Page 111: ... 09 Operation 09 111 124 ...
Page 125: ... 10 CDP control panel 10 125 148 ...
Page 149: ... 11 Preventive and corrective maintenance 11 149 172 ...
Page 173: ......