10.3.3.1. Overview
If the parameter lock is disabled or unlocked (see
), the parameters mode allows entering the parameter
settings for the required drive configuration depending on the application.
The parameters are organized in functional groups, so called parameter groups.
For details about the parameters, their settings and functions, see
“Appendix G
-
Signal and parameter table”.
When entering the parameter mode for the first time after the auxiliary voltage of
the drive has been switched on, the CDP control panel displays the first parameter
of parameter
group 99
. The next time the parameters mode is entered, the
previously selected parameter displays.
Some parameter values cannot be changed while the drive is running. If tried, the
following warning displays.
Table 10
-
1 Parameter groups
Group
Description
Group 07
Control words
Group 08
Status words
Group 09
Fault and alarm words
Group 11
Start, stop, direction, MCB and control
Group 12
Reference selection
Group 13
Basic analog inputs
Group 14
Basic digital outputs
Group 15
Basic analog outputs
Group 16
System control inputs
Group 17
Utilities
Group 18
Process speed
Group 19
Data storage
Group 20
Limits
Group 21
Start, stop and process stop
Group 22
Ramp functions
Group 23
Speed reference
** Warning **
Write Access Denied
Parameter Setting
Not Posssible