Chapter 3 – ACS 502 Installation Instructions
ACS 502 Installation & Start-up Manual
3-5
Output Power Wiring
Table 3-3 shows the output wire sizes for the ACS 502.
Table 3-3
ACS 502 Output Wire Sizes
* Indicates 2 pole per phase for terminal information and 2 conductor for wire
size information.
Table 3-4 shows ground lug wire sizes for the ACS 502.
Table 3-4
ACS 502 Ground Lug Wire Sizes
Amp Range
Overload
Terminal Block
29.3 – 60.0
#12 – #2
#6-250MCM
57.1 – 100.0
#10 – 2/0
#6-250MCM
98.0 – 180.0
#6 – 250MCM
#6-250MCM
175.0 – 220.0
* #6 – 4/0
* #6-4/0
221.0 – 465.0
* #6 – 4/0
* #6-4/0
Drive Type
Ground Lug
ACS 502-050 to ACS 502-350
#6-350MCM