82 Electrical installation
Jumpers
DI/DIO grounding selector (located between XD24 and XDI) – Determines whether the
DIGND (ground for digital inputs DI1…DI4) floats, or if it is connected to DIOGND (ground
for DI5 DIO1 and DIO2). See the JCU isolation and grounding diagram on page
If DIGND floats, the common of digital inputs DI1…DI4 should be connected to XD24:2.
The common can be either GND or V
cc
as DI1…DI4 are of the NPN/PNP type.
AI1 – Determines whether analog input AI1 is used as a current or voltage input.
AI2 – Determines whether analog input AI2 is used as a current or voltage input.
T – Drive-to-drive link termination. Must be set to the ON position when the drive is the last
unit on the link.
1
DIGND floats
DIGND tied to DIOGND
XD24
2
4
2
3
1
XD24
2
4
2
3
AI1
AI2
1
7
AI1
AI2
1
7
Current
Voltage
AI1
AI2
1
7
AI1
AI2
1
7
Current
Voltage
T
Termination ON
Termination OFF
T
Summary of Contents for ACQ810
Page 1: ...ABB industrial drives Hardware manual ACQ810 drive modules 200 to 400 kW 250 to 600 hp...
Page 4: ......
Page 16: ...16 Safety instructions...
Page 30: ...30 Operation principle and hardware description...
Page 69: ...Planning the electrical installation 69 Example circuit diagram See page 129...
Page 70: ...70 Planning the electrical installation...
Page 88: ...88 Electrical installation...
Page 94: ...94 Start up...
Page 96: ...96 Fault tracing...
Page 122: ...122 Dimension drawings Frame without pedestal mm 64801082_3 6 E Center of gravity...
Page 123: ...Dimension drawings 123 Frame with busbars on the left side mm 64801082_5 6 E...
Page 125: ...Dimension drawings 125 Package...
Page 128: ...128 Dimension drawings...
Page 132: ...132 du dt filters and sine filters Sine filters Contact your local ABB representative...