58 Planning the electrical installation
Alternative power cable types
The power cable types that can be used with the drive are represented below.
Motor cable shield
To effectively suppress radiated and conducted radio-frequency emissions, the cable
shield conductivity must be at least 1/10 of the phase conductor conductivity. The
requirements are easily met with a copper or aluminium shield. The minimum requirement
of the motor cable shield of the drive is shown below. It consists of a concentric layer of
copper wires with an open helix of copper tape or copper wire. The better and tighter the
shield, the lower the emission level and bearing currents.
Additional US requirements
Use type MC continuous corrugated aluminum armor cable with symmetrical grounds or
shielded power cable for the motor cables if metallic conduit is not used. For the North
American market, 600 V AC cable is accepted for up to 500 V AC. For drives rated over
100 amperes, the power cables must be rated for 75
°
C (167
°
F).
Symmetrical shielded cable: three phase conductors
and a concentric or otherwise symmetrically
constructed PE conductor, and a shield
Recommended
PE conductor
and shield
Shield
Shield
A separate PE conductor is required if the
conductivity of the cable shield is < 50% of the
conductivity of the phase conductor.
A four-conductor
system: three phase
conductors and a
protective conductor
Shield
PE
PE
PE
Not allowed for motor cables
with
phase conductor cross section larger
than 10 mm
2
(motors > 30 kW [40 hp]).
Not allowed for motor cables
Insulation jacket
Copper wire screen
Helix of copper tape
or copper wire
Cable core
Inner insulation
Summary of Contents for ACQ810
Page 1: ...ABB industrial drives Hardware manual ACQ810 drive modules 200 to 400 kW 250 to 600 hp...
Page 4: ......
Page 16: ...16 Safety instructions...
Page 30: ...30 Operation principle and hardware description...
Page 69: ...Planning the electrical installation 69 Example circuit diagram See page 129...
Page 70: ...70 Planning the electrical installation...
Page 88: ...88 Electrical installation...
Page 94: ...94 Start up...
Page 96: ...96 Fault tracing...
Page 122: ...122 Dimension drawings Frame without pedestal mm 64801082_3 6 E Center of gravity...
Page 123: ...Dimension drawings 123 Frame with busbars on the left side mm 64801082_5 6 E...
Page 125: ...Dimension drawings 125 Package...
Page 128: ...128 Dimension drawings...
Page 132: ...132 du dt filters and sine filters Sine filters Contact your local ABB representative...