34 Planning the cabinet installation
Arranging the grounding inside the cabinet
Arrange proper grounding for any cross-members or shelves on which components are
mounted:
•
Leaving the component connecting surfaces unpainted will form a proper grounding
contact to the cabinet frame.
•
The drive module will be grounded to the cabinet frame via its fastening screws.
Selecting busbar material and preparation of the joints
If planning the use of busbars, note the following:
•
Tin-plated copper is recommended. Aluminium can also be used.
•
For the joints of aluminium busbars, the oxide layer must be removed and suitable
anti-oxidant joint compound applied.
Tightening torques
Apply the following torques to grade 8.8 screws (with or without joint compound) that
tighten electric contacts.
Planning the fastening of the cabinet
Note the following when planning the fastening of the cabinet:
•
The cabinet must be fastened to the floor from front and back.
•
If fastening at the back is not possible or the cabinet will be exposed to vibration, the
cabinet must be fastened at the top to the rear wall/roof.
WARNING!
Do not fasten the cabinet by electric welding if the drive module is
already installed inside the cabinet. ABB does not assume any liability for
damages caused by electric welding as the welding circuit may damage electronic
circuits in the cabinet.
Screw size
Torque
M5
3.5 N·m (2.6 lbf·ft)
M6
9 N·m (6.6 lbf·ft)
M8
20 N·m (14.8 lbf·ft)
M10
40 N·m (29.5 lbf·ft)
M12
70 N·m (52 lbf·ft)
M16
180 N·m (133 lbf·ft)
Summary of Contents for ACQ810
Page 1: ...ABB industrial drives Hardware manual ACQ810 drive modules 200 to 400 kW 250 to 600 hp...
Page 4: ......
Page 16: ...16 Safety instructions...
Page 30: ...30 Operation principle and hardware description...
Page 69: ...Planning the electrical installation 69 Example circuit diagram See page 129...
Page 70: ...70 Planning the electrical installation...
Page 88: ...88 Electrical installation...
Page 94: ...94 Start up...
Page 96: ...96 Fault tracing...
Page 122: ...122 Dimension drawings Frame without pedestal mm 64801082_3 6 E Center of gravity...
Page 123: ...Dimension drawings 123 Frame with busbars on the left side mm 64801082_5 6 E...
Page 125: ...Dimension drawings 125 Package...
Page 128: ...128 Dimension drawings...
Page 132: ...132 du dt filters and sine filters Sine filters Contact your local ABB representative...