![ABB ACQ810 Hardware Manual Download Page 112](http://html1.mh-extra.com/html/abb/acq810/acq810_hardware-manual_3423066112.webp)
112 Technical data
Losses, cooling data and noise
IP22 cabinet with no extra fan
An IP22 cabinet should meet the following data to ensure efficient cooling of the drive
module. No extra fan is used. The pressure drop over the cabinet is the additional
counterpressure that the module fan is capable of overcoming while still maintaining the
required air flow through the module.
IP54 cabinet with an extra fan
An IP54 cabinet should meet the following data to ensure efficient cooling of the drive
module. An extra fan is used. The pressure drop over the cabinet is the counterpressure
the extra fan must overcome. The given fan types and filter materials are examples.
Corresponding products by another manufacturer may be used as well. See the
manufacturer’s Internet site for the detailed specification.
Drive type
Frame
size
Air flow
Heat
dissipation
Noise
m
3
/h
ft
3
/min
W
dB
ACQ810-302A-4
R8
1220
718
5000
72
ACQ810-361A-4
R8
1220
718
6000
72
ACQ810-414A-4
R8
1220
718
6850
72
ACQ810-477A-4
R8
1220
718
7800
72
ACQ810-550A-4
R8
1220
718
8100
72
ACQ810-616A-4
R8
1220
718
9100
72
ACQ810-704A-4
R8
1220
718
9700
72
00581898
Temperature rise over
module
30 °C
Pressure drop
300 Pa (over module), 45 Pa over cabinet
Cabinet air inlet
Minimum size (mm): 288×292+688×521
Filter by Luftfilter: airTex G150
Cabinet air outlet size
398 mm × 312 mm (2 pcs) when the outlet is located on the cabinet roof
00096931
Temperature rise over
module
30 °C
Pressure drop
250 Pa (over cabinet), average, air filters moderately congested
Extra fan type
RH35M-4EK.2F.1R by Ziehl-Abegg or RB4T-355/170 by ebm
Air inlet filter by Luftfilter
airComp 300-50,
Minimum size in door (mm): 288×292 + 688×521
Air outlet filter by
Luftfilter
airTex G150
Minimum size at roof (mm): 398×312 (2 pcs)
00096931
Summary of Contents for ACQ810
Page 1: ...ABB industrial drives Hardware manual ACQ810 drive modules 200 to 400 kW 250 to 600 hp...
Page 4: ......
Page 16: ...16 Safety instructions...
Page 30: ...30 Operation principle and hardware description...
Page 69: ...Planning the electrical installation 69 Example circuit diagram See page 129...
Page 70: ...70 Planning the electrical installation...
Page 88: ...88 Electrical installation...
Page 94: ...94 Start up...
Page 96: ...96 Fault tracing...
Page 122: ...122 Dimension drawings Frame without pedestal mm 64801082_3 6 E Center of gravity...
Page 123: ...Dimension drawings 123 Frame with busbars on the left side mm 64801082_5 6 E...
Page 125: ...Dimension drawings 125 Package...
Page 128: ...128 Dimension drawings...
Page 132: ...132 du dt filters and sine filters Sine filters Contact your local ABB representative...