![ABB ACQ810 Hardware Manual Download Page 107](http://html1.mh-extra.com/html/abb/acq810/acq810_hardware-manual_3423066107.webp)
Technical data 107
Fuses (IEC)
gG and aR fuses for protection against short-circuit in the input power cable or drive are
listed below. Either fuse type may be used if it operates rapidly enough. Choose between
gG and aR fuses according to the table under
Quick guide for selecting between gG and
on page
or verify the operating time by
checking that the short-circuit
current of the installation is at least the value given in the fuse table
. The short-circuit
current can be calculated as follows:
where
I
k2-ph
= short-circuit current in symmetrical two-phase short-circuit (A)
U
= network line-to-line voltage (V)
R
c
= cable resistance (ohm)
Z
k
= z
k
·
U
N
2
/
S
N
= transformer impedance (ohm)
z
k
= transformer impedance (%)
U
N
= transformer rated voltage (V)
S
N
= nominal apparent power of the transformer (kVA)
X
c
= cable reactance (ohm).
Calculation example
Drive:
•
ACQ810-04-414A-4
•
supply voltage
U
= 410 V
Transformer:
•
rated power
S
N
= 3000 kVA
•
rated voltage
U
N
= 430 V
•
transformer impedance z
k
= 7.2%.
Supply cable:
•
length = 170 m
•
resistance/length = 0.112 ohm/km
•
reactance/length = 0.0273 ohm/km.
I
k2-ph
=
2
·
R
c
2
+ (
Z
k
+
X
c
)
2
U
·
(430 V)
2
3000 kVA
= 4.438 mohm
Z
k
= z
k
·
U
N
2
S
N
= 0.072
m
·
0.112
ohm
km
= 19.04 mohm
R
c
= 170
Summary of Contents for ACQ810
Page 1: ...ABB industrial drives Hardware manual ACQ810 drive modules 200 to 400 kW 250 to 600 hp...
Page 4: ......
Page 16: ...16 Safety instructions...
Page 30: ...30 Operation principle and hardware description...
Page 69: ...Planning the electrical installation 69 Example circuit diagram See page 129...
Page 70: ...70 Planning the electrical installation...
Page 88: ...88 Electrical installation...
Page 94: ...94 Start up...
Page 96: ...96 Fault tracing...
Page 122: ...122 Dimension drawings Frame without pedestal mm 64801082_3 6 E Center of gravity...
Page 123: ...Dimension drawings 123 Frame with busbars on the left side mm 64801082_5 6 E...
Page 125: ...Dimension drawings 125 Package...
Page 128: ...128 Dimension drawings...
Page 132: ...132 du dt filters and sine filters Sine filters Contact your local ABB representative...