The ACQ810 control panel 35
Fault Logger
In the Fault Logger option, you can:
• view the drive fault history
• see the details of the most recent faults
• read the help text for the fault and make corrective actions
• start, stop, change the direction and switch between local and remote control.
How to view faults
Step
Action
Display
1.
Go to the Main menu by pressing
if you are in the
Output mode.
Otherwise press
repeatedly until you get to the
Main menu.
2.
Go to the Fault Logger option by selecting FAULT
LOGGER on the menu with keys
and
, and
pressing .
If there are no faults in the fault history, corresponding
text will be shown.
If there is a fault history, the display shows the fault log
starting with the most recent fault. The number on the
row is the fault code according to which the causes and
corrective actions are listed in chapter
(page
3.
To see the details of a fault, select it with keys
and
, and press
.
Scroll the text with keys
and
.
To return to the previous display, press
.
4.
If you want help in diagnosing the fault, press
.
MENU
EXIT
PARAMETERS
ASSISTANTS
CHANGED PAR
EXIT
ENTER
00:00
MAIN MENU
1
LOC
ENTER
No fault history
found
MESSAGE
LOC
36: LOCAL CTRL LOSS
29.04.08 10:45:58
FAULT LOGGER
EXIT
DETAIL
00:00
LOC
1
DETAIL
EXIT
TIME
10:45:58
FAULT CODE
36
FAULT CODE EXTENSION
LOCAL CTRL LOSS
EXIT
DIAG
00:00
LOC
DIAG
Check parameter ‘30.0
3 Local ctrl loss’ se
tting. Check PC tool
or panel connection.
EXIT
OK
LOC
Summary of Contents for ACQ810
Page 1: ...ABB industrial drives Firmware manual Standard pump control program for ACQ810 drives ...
Page 4: ......
Page 14: ...14 About the manual ...
Page 56: ...56 Control locations ...
Page 97: ...Application macros 97 ...
Page 98: ...98 Application macros ...
Page 100: ...100 Application macros ...
Page 101: ...Application macros 101 ...
Page 106: ...106 Application macros 75 01 Operation mode Multipump 76 01 Enable MF comm Yes ...
Page 356: ...356 Control through the embedded fieldbus interface ...
Page 366: ...366 Control through a fieldbus adapter ...
Page 374: ...374 Control block diagrams ...