Parameters 139
10.17
Start enable
Selects the source for the Start enable signal.
1 = Start enable.
If the signal is switched off, the drive will not start or coasts to
stop if running.
DI1
Digital input DI1 (as indicated by
, bit 0).
1073742337
DI2
Digital input DI2 (as indicated by
, bit 1).
1073807873
DI3
Digital input DI3 (as indicated by
, bit 2).
1073873409
DI4
Digital input DI4 (as indicated by
, bit 3).
1073938945
DI5
Digital input DI5 (as indicated by
, bit 4).
1074004481
Const
Bit pointer setting (see
on page
-
Pointer
10.19
Start inhibit
Enables the start inhibit function. The function prevents drive
restart (i.e. protects against unexpected start) if
• the drive trips on a fault and the fault is reset,
• the run enable signal is activated while the start command
),
• control changes from local to remote, or
• external control switches from EXT1 to EXT2 or vice versa.
A new rising edge of the start command is needed after the
start inhibit has been activated.
Note that in certain applications it is necessary to allow the
drive to restart.
Disabled
The start inhibit function is disabled.
0
Enabled
The start inhibit function is enabled.
1
10.20
Start intrl func
Defines how the start interlock input (DIIL) on the JCU
control unit affects the drive operation.
Off2 stop
With the drive running:
• 1 = Normal operation.
• 0 = Stop by coasting. The drive can be restarted by
restoring the start interlock signal and switching the start
signal from 0 to 1.
With the drive stopped:
• 1 = Starting allowed.
• 0 = Starting not allowed.
0
Off3 stop
With the drive running:
• 1 = Normal operation.
• 0 = Stop by ramping. The deceleration time is defined by
parameter
. The drive can be restarted
by restoring the start interlock signal and switching the
start signal from 0 to 1.
With the drive stopped:
• 1 = Starting allowed.
• 0 = Starting not allowed.
1
No.
Name/Value
Description
FbEq
Summary of Contents for ACQ810
Page 1: ...ABB industrial drives Firmware manual Standard pump control program for ACQ810 drives ...
Page 4: ......
Page 14: ...14 About the manual ...
Page 56: ...56 Control locations ...
Page 97: ...Application macros 97 ...
Page 98: ...98 Application macros ...
Page 100: ...100 Application macros ...
Page 101: ...Application macros 101 ...
Page 106: ...106 Application macros 75 01 Operation mode Multipump 76 01 Enable MF comm Yes ...
Page 356: ...356 Control through the embedded fieldbus interface ...
Page 366: ...366 Control through a fieldbus adapter ...
Page 374: ...374 Control block diagrams ...