374 Fieldbus control through a fieldbus adapter
5
Ramp hold
1
ramp function.
Proceed to
RAMP FUNCTION GENERATOR: ACCELERATOR D
.
0
Halt ramping (Ramp Function Generator output held).
6
Ramp in zero
1
Normal operation. Proceed to
OPERATING
.
Note:
This bit is effective only if the fieldbus interface is set as
the source for this signal by drive parameters.
0
Force Ramp function generator input to zero.
7
Reset
0=>1
Fault reset if an active fault exists. Proceed to
SWITCH-ON
INHIBITED
.
Note:
This bit is effective only if the fieldbus interface is set as
the source of the reset signal by drive parameters.
0
Continue normal operation.
8...9
Reserved
10
Remote cmd
1
Fieldbus control d.
0
Control word and reference not getting through to the drive,
except for bits 0…2.
11
Ext ctrl loc
1
Select External Control Location EXT2. Effective if control
location is parameterized to be selected from fieldbus.
0
Select External Control Location EXT1. Effective if control
location is parameterized to be selected from fieldbus.
12
User bit 0
1
User configurable
0
13
User bit 1
1
0
14
User bit 2
1
0
15
User bit 3
1
0
Bit
Name
Value STATE/Description
Summary of Contents for ACQ80
Page 1: ... ABB DRIVES FOR WATER ACQ80 standard program control Firmware manual ...
Page 2: ... Related documents are listed on page 13 ...
Page 4: ......
Page 10: ...10 Table of contents ...
Page 32: ...32 Startup control with I O and ID run ...
Page 34: ...34 Using the control panel ...
Page 74: ...74 Program features ...
Page 78: ...78 Control macros ...
Page 380: ...380 Fieldbus control through a fieldbus adapter ...
Page 384: ...384 Parameterization with Drive Composer ...
Page 388: ...388 Parameterization with Automation builder drive manager ...