Program features 51
Critical speeds/frequencies
Critical speeds (sometimes called “skip speeds”) can be predefined for applications
where it is necessary to avoid certain motor speeds or speed ranges because of, for
example, mechanical resonance problems.
The critical speeds function prevents the reference from dwelling within a critical band
for extended times. When a changing reference (
) enters
a critical range, the output of the function (
) freezes until the
reference exits the range. Any instant change in the output is smoothed out by the
ramping function further in the reference chain.
When the drive is limiting the allowed output speeds/frequencies, it limits to the
absolutely lowest critical speed (critical speed low or critical frequency low) when
accelerating from standstill, unless the speed reference is over the upper critical
speed/ frequency limit.
The function is also available for scalar motor control with a frequency reference. The
input of the function is shown by
Example
A pump has vibrations in the range of 540…690 rpm and 1380…1560 rpm. To make
the drive avoid these speed ranges,
• the critical speeds function by turning on bit 0 of parameter
, and
• set the critical speed ranges as in the figure below.
Settings
(page
• Critical frequencies: parameters
…
).
540
690
1380
1560
1
Par.
= 540 rpm
2
Par.
= 690 rpm
3
Par.
= 1380 rpm
4
Par.
= 1560 rpm
1
2
3
4
(rpm)
(output of function)
(rpm)
(input of function)
Summary of Contents for ACQ580
Page 1: ...ABB drives for water Firmware manual ACQ580 pump control program ...
Page 4: ... 2017 ABB Oy All Rights Reserved 3AXD50000035867 Rev C EN EFFECTIVE 2017 06 21 ...
Page 30: ...26 Start up control with I O and ID run ...
Page 40: ...36 Default configuration ...
Page 304: ...300 Parameters ...
Page 340: ...336 Additional parameter data ...