Fault tracing 351
Fault messages
Code
(hex)
Fault / Aux. code
Cause
What to do
1080
Backup/Restore
timeout
Panel or PC tool has failed to
communicate with the drive
when backup was being made
or restored.
Request backup or restore again.
1081
Rating ID fault
Drive software has not been
able to read the rating ID of the
drive.
Reset the fault to make the drive try to
reread the rating ID.
If the fault reappears, cycle the power
to the drive. You may have to be
repeat this. If the fault persists,
contact your local ABB
representative.
2310
Overcurrent
Output current has exceeded
internal fault limit.
In addition to an actual
overcurrent situation, this fault
may also be caused by an
earth fault or supply phase
loss.
Check motor load.
Check acceleration times in
parameter group
(frequency control).
and
.
Check motor and motor cable
(including phasing and delta/star
connection).
Check there are no contactors
opening and closing in motor cable.
Check that the start-up data in
parameter group 99 corresponds to
the motor rating plate.
Check that there are no power factor
correction capacitors or surge
absorbers in motor cable.
Check for an earth fault in motor or
motor cables by measuring the
insulation resistances of motor and
motor cable. See chapter
Electrical
installation
, section
Checking the
insulation of the assembly
in the
Hardware manual
of the drive.
2330
Earth leakage
Programmable fault:
Drive has detected load
unbalance typically due to
earth fault in motor or motor
cable.
Check there are no power factor
correction capacitors or surge
absorbers in motor cable.
Check for an earth fault in motor or
motor cables by measuring the
insulation resistances of motor and
motor cable.
Try running the motor in scalar control
mode if allowed. (See parameter
.)
If no earth fault can be detected,
contact your local ABB
representative.
Summary of Contents for ACQ580
Page 1: ...ABB drives for water Firmware manual ACQ580 pump control program ...
Page 4: ... 2017 ABB Oy All Rights Reserved 3AXD50000035867 Rev C EN EFFECTIVE 2017 06 21 ...
Page 30: ...26 Start up control with I O and ID run ...
Page 40: ...36 Default configuration ...
Page 304: ...300 Parameters ...
Page 340: ...336 Additional parameter data ...