20 Start-up, control with I/O and ID run
How to control the drive through the I/O interface
The table below describes how to operate the drive through the digital and analog
inputs when:
• the motor start-up is performed, and
• the default parameter settings of the Water default configurations are in use.
Preliminary settings
If you need to change the direction of rotation, check
that limits allow reverse direction: Check parameter
group
and make sure that the minimum limit
has a negative value and the maximum limit has a
positive value.
Default settings only allow forward direction.Note that
efficient pump cleaning can require reverse speed.
Make sure that the control connections are wired
according to the connection diagram given for the
Water default.
See section
on page
.
Make sure that the drive is in external control. To
switch to external control, press key
.
In external control, the panel display
shows text
Auto
at the top left.
Starting and controlling the speed of the motor
Start by switching digital input DI1 on.
The arrow starts rotating. It is dotted until the setpoint
is reached.
Regulate the drive output frequency (motor speed) by
adjusting voltage of analog input AI1.
Stopping the motor
Switch digital input DI1 off. The arrow stops rotating.
Auto
Summary of Contents for ACQ580
Page 1: ...ABB drives for water Firmware manual ACQ580 pump control program ...
Page 4: ... 2017 ABB Oy All Rights Reserved 3AXD50000035867 Rev C EN EFFECTIVE 2017 06 21 ...
Page 30: ...26 Start up control with I O and ID run ...
Page 40: ...36 Default configuration ...
Page 304: ...300 Parameters ...
Page 340: ...336 Additional parameter data ...