Parameters 109
Diagnostic word 3. For possible causes and remedies, see
chapter
-
0000h…FFFFh
Diagnostic word 3.
1 = 1
No.
Name/Value
Description
Def/FbEq16
Bit
Name
Value
0
Main circuit pwr
ON
Yes = Main circuit power is on.
1
Ext. pwr supply
Yes = Control board is powered on from external power supply, for
example, user provided 24 V.
2
Programming
wand
Yes = Control board is powered on by the Programming wand tool
for offline programming or parameterization. Main circuit / power unit
is without power.
3
Panel port comm
loss
Yes = Panel port communication lost.
4
Reserved
5
Field bus force trip Yes = Fault trip forced (requested) from a field bus.
6
Start inhibited
Yes = Start inhibited (prevented) due to some reason for example
interlock.
7
Safe Torq Off
Yes = Safe Torque Off fault active.
8
STO broken
Yes = Safe Torque Off circuitry is broken.
9
kWh pulse
Yes = kWh pulse is active.
10
Reserved
11
Fan command
On = Drive fan is rotating above idle speed.
12…15 Reserved