Supplemental Installation Manual for ACQ580-Px

ACQ580-PC/PD

Branch circuit protection

Input power is connected to the ACQ580 through a door interlocked disconnect 
switch or circuit breaker. When connected to a 240V or 480V power source, the 
ACQ580 with the circuit breaker option is suitable for use on a circuit capable of 
delivering not more than 100,000 RMS symmetrical amperes. When connected to a 
600V power source, PC configurations are suitable for use on a circuit capable of 
delivering not more than 25,000 RMS symmetrical amperes (2-30 HP).

Fuses

Note: 

The UL listed drive fuses in the table are provided in the purchased product. 

• Replacement fuses are required to be of the same class, current rating, and 

voltage rating. Fuses from other manufacturers can be used if they are 600V 
rated and meet the specifications given in the table. 

• Fuses with higher current rating than specified must not be used. 

208 Volt fuses for packaged drive

208 Volt

Nominal Output 

Range

Base 

Drive 

Frame 

Size

Internal Drive

 Fuse Rating

External Fuse for

Disconnect Option

Type Code

1

Drive 

Current

Packag

e Power

A

HP

Class

Current 

Rating

Class

Max Current 

Rating

ACQ580-Px-04A6-2

4.6

1

R1

Class CC

15A

N/A

N/A

ACQ580-Px-06A6-2

6.6

1.5

R1

Class CC

15A

N/A

N/A

ACQ580-Px-07A5-2

7.5

2

R1

Class CC

15A

N/A

N/A

ACQ580-Px-10A6-2

10.6

3

R1

Class CC

15A

N/A

N/A

ACQ580-Px-017A-2

16.7

5

R1

Class CC

30A

N/A

N/A

ACQ580-Px-024A-2

24.2

7.5

R2

Class CC

30A

N/A

N/A

ACQ580-Px-031A-2

30.8

10

R2

Class T

40A

N/A

N/A

ACQ580-Px-046A-2

46.2

15

R3

Class T

80A

N/A

N/A

ACQ580-Px-059A-2

59.4

20

R3

Class T

80A

N/A

N/A

ACQ580-Px-075A-2

74.8

25

R4

Class T

100A

N/A

N/A

1) “Px” represents both PC and PD.

Summary of Contents for ACQ580-P Series

Page 1: ...ACQ580 Px Supplement Installation Manual for ACQ580 PC PD ACQ580 PC PD Packaged Drives with Disconnect 1 60 HP...

Page 2: ......

Page 3: ...dges Handle the drive carefully Frames R5 R9 Lift the drive with a lifting device Use the lifting eyes of the drive Frames R5 R9 Do not tip the drive over The drive is heavy and its center of gravity...

Page 4: ...art immediately after fault reset See parameters 20 02 Ext1 start trigger type and 20 07 Ext2 start trigger type in ACQ580 Pump control program firmware manual 3AXD50000035867 English When the control...

Page 5: ...and corner grounded TN systems North America in ACQ580 Hardware Manual Note For other systems connecting the internal EMC filter will reduce the conducted emission If the drive will be connected on a...

Page 6: ...rference In a multiple drive installation connect each drive separately to the protective earth PE bus of the power supply Make sure that the conductivity of the protective earth PE conductors is suff...

Page 7: ...C UDC and the grounding PE terminal is close to 0 V Install temporary grounding to the drive output terminals T1 U T2 V T3 W Connect the output terminals together as well as to the PE Start up and ope...

Page 8: ...f data installation of anti virus programs etc to protect the product the network its system and the interface against any kind of security breaches unauthorized access interference intrusion leakage...

Page 9: ...type of your drive refer to its construction code on either Serial number label attached on upper part of the top mounting plate between the mounting holes Type code label attached to the base frame o...

Page 10: ...ervicing the drive Failure to disconnect power may cause serious injury or death 1 Install wiring WARNING Metal shavings or debris in the enclosure can damage electrical equipment and create a hazardo...

Page 11: ...iring access from the bottom only The following figures show the layout and wiring connection points For drive control wiring see US Quick Start Guide 3AXD50000049128 Maintain appropriate separation o...

Page 12: ...emental Installation Manual for ACQ580 Px ACQ580 PC PD Disconnect Switch or Circuit Breaker Motor Ground Lug Fuses P3 P4 Input Ground Lug Input Terminals Motor Terminals Px1 3 Px12 3 Px1 4 Px12 4 ACQ5...

Page 13: ...UL NEMA Type 1 and 12 Motor Terminals Ground Lugs UL NEMA Type 1 and 12 ACQ580 Px 04A6 2 4 6 1 R1 10 62 in lbs 10 55 in lbs 10 0 7 ft lbs 2 50 in lbs ACQ580 Px 06A6 2 6 6 1 5 R1 ACQ580 Px 07A5 2 7 5 2...

Page 14: ...2 50 in lbs ACQ580 Px 03A0 4 3 1 5 R1 ACQ580 Px 03A5 4 3 5 2 R1 ACQ580 Px 04A8 4 4 8 3 R1 ACQ580 Px 07A6 4 7 6 5 R1 ACQ580 Px 012A 4 12 7 5 R1 ACQ580 Px 014A 4 14 10 R2 10 62 in lbs 8 55 in lbs 6 1 1...

Page 15: ...in lbs 10 55 in lbs 6 1 1 ft lbs 2 50 in lbs ACQ580 Px 03A9 6 3 9 3 R2 12 62 in lbs ACQ580 Px 06A1 6 6 1 5 R2 10 62 in lbs ACQ580 Px 09A0 6 9 7 5 R2 ACQ580 Px 011A 6 11 10 R2 ACQ580 Px 017A 6 17 15 R...

Page 16: ...es from other manufacturers can be used if they are 600V rated and meet the specifications given in the table Fuses with higher current rating than specified must not be used 208 Volt fuses for packag...

Page 17: ...0 Px 044A 4 44 30 R3 Class T 60A N A N A ACQ580 Px 052A 4 52 40 R4 Class T 80A N A N A ACQ580 Px 065A 4 65 50 R4 Class T 90A N A N A ACQ580 Px 077A 4 77 60 R4 Class T 100A N A N A 1 Px represents both...

Page 18: ...dle The operating handle can be padlocked in the OFF position padlock not supplied Enclosure options are UL NEMA Type 1 and UL NEMA Type 12 NEMA 1 and NEMA 12 The following is a typical power diagram...

Page 19: ...19 Supplemental Installation Manual for ACQ580 Px ACQ580 PC PD Dimensions P1 Type 1...

Page 20: ...Supplemental Installation Manual for ACQ580 Px 20 ACQ580 PC PD P1 Type 12...

Page 21: ...21 Supplemental Installation Manual for ACQ580 Px ACQ580 PC PD P2 Type 1...

Page 22: ...Supplemental Installation Manual for ACQ580 Px 22 ACQ580 PC PD P2 Type 12...

Page 23: ...23 Supplemental Installation Manual for ACQ580 Px ACQ580 PC PD P3 Type 1...

Page 24: ...Supplemental Installation Manual for ACQ580 Px 24 ACQ580 PC PD P3 Type 12...

Page 25: ...25 Supplemental Installation Manual for ACQ580 Px ACQ580 PC PD P4 Type 1...

Page 26: ...Supplemental Installation Manual for ACQ580 Px 26 ACQ580 PC PD P4 Type 12...

Page 27: ......

Page 28: ...3AXD50000459698REVA Effective 2019 09 01 Supersedes ABB Inc 16250 West Glendale Drive New Berlin WI 53151 USA Telephone 1 800 752 0696 Fax 1 262 785 0397 Internet www abb com drives...

Reviews: