![ABB ACQ580-34 Hardware Manual Download Page 42](http://html.mh-extra.com/html/abb/acq580-34/acq580-34_hardware-manual_2546042.webp)
Place the control board(s) away from:
• main circuit components such as contactors, switches and power cables
• hot parts (heatsink, air outlet of the drive module).
■
Grounding of mounting structures
Arrange the grounding of the module by leaving the contact surfaces of the fastening points
unpainted (bare metal-to-metal contact). The module frame is grounded to the PE busbar
of the cabinet via the fastening surfaces, screws and the cabinet frame. Alternatively, use
a separate grounding conductor between the PE terminal of the module and the PE busbar
of the cabinet.
Ground also the other components in the cabinet according to the principle above.
■
Busbar material and joints
ABB recommends tin-plated copper, but aluminum can also be used.
Note:
Before joining aluminum busbars, remove the oxide layer and apply suitable
anti-oxidant joint compound.
■
Shrouds
The installation of shrouds (touch protection) to fulfill applicable safety regulations is the
responsibility of the drive system builder.
Ready-made shrouding parts are available from ABB for some cabinet designs, see the
ordering information.
■
Tightening torques
Unless a tightening torque is specified in the text, the following torques can be used.
Electrical connections
Strength class
Torque
Size
4.6...8.8
0.5 N·m (4.4 lbf·in)
M3
4.6...8.8
1 N·m (9 lbf·in)
M4
8.8
4 N·m (35 lbf·in)
M5
8.8
9 N·m (6.6 lbf·ft)
M6
8.8
22 N·m (16 lbf·ft)
M8
8.8
42 N·m (31 lbf·ft)
M10
8.8
70 N·m (52 lbf·ft)
M12
8.8
120 N·m (90 lbf·ft)
M16
Mechanical connections
Strength class
Max. torque
Size
8.8
6 N·m (53 lbf·in)
M5
8.8
10 N·m (7.4 lbf·ft)
M6
8.8
24 N·m (17.7 lbf·ft)
M8
42 Generic cabinet planning instructions
Summary of Contents for ACQ580-34
Page 1: ... ABB DRIVES FOR WATER ACQ580 34 drive modules Hardware manual ...
Page 2: ......
Page 4: ......
Page 14: ...14 ...
Page 24: ...24 ...
Page 50: ...50 ...
Page 60: ...60 ...
Page 70: ...70 ...
Page 94: ...94 ...
Page 110: ...110 ...
Page 122: ...122 ...
Page 132: ...Dimension drawing 132 External control unit option P906 ...
Page 140: ...140 ...
Page 144: ...144 ...
Page 164: ...164 ...
Page 184: ...Standard configuration E208 and E210 included 184 Dimension drawings ...
Page 185: ...Drive module with option B051 Dimension drawings 185 ...
Page 186: ...Drive module with options B051 H370 186 Dimension drawings ...
Page 187: ...LCL filter module Dimension drawings 187 ...
Page 190: ...190 ...
Page 208: ... Declaration of conformity 208 The Safe torque off function ...
Page 214: ...214 ...
Page 226: ...226 ...