Harmonics are below the limits defined in IEEE 519-2014, and G5/4. The drive
complies with IEC 61000-3-2, IEC 61000-3-4 and IEC 61000-3-12.
Harmonic distortion
The table below shows typical values of the drive for short-circuit ratio (
I
sc
/
I
1
) of 20
to 100. The values will be met if the supply network voltage is not distorted by
other loads and when the drive operates at nominal load.
THDv (%)
THDi (%)
Nominal bus voltage V at PCC
< 3**
3*
V ≤ 690 V
Point on a public power supply system, electrically nearest to a particular
load, at which other loads are, or could be, connected. The PCC is a point
located upstream of the considered installation.
PCC
Indicates the total harmonic current distortion of the wave form. This value
is defined as the ratio (in %) of the harmonic current to the fundamental
(non-harmonic) current measured at a load point at the particular moment
when the measurement is taken:
THDi =
40
2
n
2
∑
I
I
1
•
100%
THDi
Indicates the total magnitude of the voltage distortion. This value is defined
as the ratio (in %) of the harmonic voltage to the fundamental (non-har-
monic) voltage:
THDv =
40
2
n
2
∑
U
U
1
•
100%
THDv
Short-circuit ratio
I
sc
/
I
1
Maximum short-circuit current at PCC
I
sc
Continuous rms input current of the drive
I
1
Amplitude of the current harmonic n
I
n
Supply voltage
U
1
Amplitude of the voltage harmonic n
U
n
* The short-circuit ratio can influence the THDi value
** Other loads can influence the THDv value
Motor connection data
Asynchronous AC induction motors, permanent magnet motors and ABB synchron-
ous reluctance motors (SynRM motors)
Motor types
0 to
U
1
nominal, can be boosted higher but requires derating. Contact ABB for
more information.
Voltage (U
2
)
0…500 Hz
Frequency (f
2
)
Note:
Operation above 150 Hz can require type-specific derating. For more inform-
ation, contact your local ABB representative.
For drives with d
u
/d
t
filter: 0…120 Hz
For drives with sine filter: 0…120 Hz
0.01 Hz
Frequency resolution
See section
Ratings
Current
Technical data 175
Summary of Contents for ACQ580-34
Page 1: ... ABB DRIVES FOR WATER ACQ580 34 drive modules Hardware manual ...
Page 2: ......
Page 4: ......
Page 14: ...14 ...
Page 24: ...24 ...
Page 50: ...50 ...
Page 60: ...60 ...
Page 70: ...70 ...
Page 94: ...94 ...
Page 110: ...110 ...
Page 122: ...122 ...
Page 132: ...Dimension drawing 132 External control unit option P906 ...
Page 140: ...140 ...
Page 144: ...144 ...
Page 164: ...164 ...
Page 184: ...Standard configuration E208 and E210 included 184 Dimension drawings ...
Page 185: ...Drive module with option B051 Dimension drawings 185 ...
Page 186: ...Drive module with options B051 H370 186 Dimension drawings ...
Page 187: ...LCL filter module Dimension drawings 187 ...
Page 190: ...190 ...
Page 208: ... Declaration of conformity 208 The Safe torque off function ...
Page 214: ...214 ...
Page 226: ...226 ...