![ABB ACQ580-01 Series Quick Installation And Start-Up Manual Download Page 104](http://html.mh-extra.com/html/abb/acq580-01-series/acq580-01-series_quick-installation-and-start-up-manual_2536104.webp)
104
R0-
R4
R5
R6-
R9
EN
DE
ES
FR
IT
RU
SV
Default I/O connections
Default I/O connections of the Water default configuration are shown below.
max.
500 ohm
1…10 kohm
X1
Reference voltage and analog inputs and outputs
1
SCR
Signal cable shield (screen)
2
AI1
Output frequency/speed reference
: 0…10 V
3
AGND
Analog input circuit common
4
+10V
Reference voltage 10 V DC
5
AI2
Actual feedback:
0…10 V
6
AGND
Analog input circuit common
7
AO1
Output frequency:
0…10 V
8
AO2
Output current:
0…20 mA
9
AGND
Analog output circuit common
X2 & X3
Aux. voltage output and programmable digital inputs
10
+24V
Aux. voltage 24 V DC, max. 250 mA
11
DGND
Aux. voltage output common
12
DCOM
Digital input common for all
13
DI1
Stop (0) / Start (1)
14
DI2
Not configured
15
DI3
Constant frequency/speed selection
16
DI4
Not configured
17
DI5
Not configured
18
DI6
Not configured
X6, X7, X8
Relay outputs
19
RO1C
Ready run
250 V AC / 30 V DC
2 A
20
RO1A
21
RO1B
22
RO2C
Running
250 V AC / 30 V DC
2 A
23
RO2A
24
RO2B
25
RO3C
Fault (-1)
250 V AC / 30 V DC
2 A
26
RO3A
27
RO3B
X5
Embedded fieldbus
29
B+
Embedded fieldbus, EFB (EIA-485)
30
A-
31
DGND
S4
TERM
Termination switch
S5
BIAS
Bias resistors switch
X4
Safe torque off
34
OUT1
Safe torque off. Factory connection. Both circuits
must be closed for the drive to start. See chapter
The Safe torque off function
in
ACQ580-01 (0.75
to 250 kW) hardware manual
(3AXD50000035866
[English]).
35
OUT2
36
SGND
37
IN1
38
IN2
Total load capacity of the Auxiliary voltage 24V (X2:10) is 6.0 W (250 mA / 24 V DC).
Wire sizes:
0.2…2.5 mm
2
(24…14 AWG): Ter24V, DGND, DCOM, B+, A-, DGND, Ext. 24V
0.14…1.5 mm
2
(26…16 AWG): Terminals DI, AI, AO, AGND, RO, STO
Tightening torques: 0.5…0.6 N·m (0.4 lbf·ft)
Summary of Contents for ACQ580-01 Series
Page 12: ... 2016 ABB Oy All Rights Reserved 3AXD50000035755 Rev A MUL EFFECTIVE 2016 03 15 ...
Page 16: ...16 R0 R4 R5 R6 R9 EN DA DE ES FI FR IT NL PL PT RU SV TR ZH ...
Page 22: ...22 R0 R4 R5 R6 R9 EN DE ES FR IT RU SV 4 3 3 R4 3 3 4 ...
Page 88: ...88 R0 R4 R5 R6 R9 ...
Page 92: ...92I 1b 1a 2 IP21 IP55 R4 1b 1 1a 2 2 IP55 R0 R2 IP55 R3 1b 1a 2 3AXD50000035755 Rev A ...
Page 94: ... 2016 ABB Oy All Rights Reserved 3AXD50000035755 Rev A MUL EFFECTIVE 2016 03 15 ...
Page 106: ...106 R0 R4 R5 R6 R9 EN DE ES FR IT RU SV ...
Page 136: ...136 FI R5 Asennuksen pikaopas R0 R4 R5 R6 R9 FI DA DE ES FI FR IT NL PL PT RU SV TR ZH ...
Page 146: ...146 FR Guide d installation R5 R0 R4 R5 R6 R9 FR DA DE ES FI FR IT NL PL PT RU SV TR ZH ...
Page 168: ...168 R0 R4 R5 R6 R9 ...
Page 171: ...171 R5 Figures F 12 G 2 3 6 6 4 5 0 5 0 6 N m 0 5 0 6 N m 5 3 ...
Page 172: ...172 H 1b 1a IP21 IP21 IP55 1b 1 2 2b 2c 3 3b 8 3c 2a 3a 3AXD50000035755 Rev A ...
Page 174: ... 2016 ABB Oy All Rights Reserved 3AXD50000035755 Rev A MUL EFFECTIVE 2016 03 15 ...
Page 180: ...180 EN Quick start up guide R0 R4 R0 R9 EN DE ES FR IT RU SV ...
Page 198: ...198 FI Pika aloitusopas R0 R4 R0 R9 FI DE ES FR IT RU SV ...
Page 204: ...204 FR Guide de mise en route R0 R4 R0 R9 FR DE ES FR IT RU SV ...
Page 216: ...216 SV Snabbguide för idrifttagning R0 R4 R0 R9 SV DE ES FR IT RU SV ...