PID Control setpoint source
Using the following settings to select the fieldbus as the setpoint source for PID
loops:
Communication fault
When using fieldbus control, specify the drive’s action if serial communication is lost.
Feedback from the drive – FBA
Inputs to the controller (drive outputs) have pre-defined meanings established by the
protocol. This feedback does not require drive configuration. The following table lists
a sample of feedback data. For a complete listing, see all parameters listed in
section
Complete parameter descriptions
Scaling
To scale the drive parameter values see the following sections, as appropriate:
•
ABB Drives profile technical data
•
Generic profile technical data
Drive parameter
Value
Setting
Protocol
reference
4010
SET
POINT
SEL
(Set 1)
8 (
COMM
VALUE
1)
9 (
COMM
+
AI
1)
10 (
COMM
*
AI
1)
Setpoint is input reference 2
(+/-/* AI1)
4110
SET
POINT
SEL
(Set 2)
4210
SET
POINT
SEL
(Ext/Trim)
Drive parameter
Value
Description
3018
COMM
FAULT
FUNC
0 (
NOT
SEL
)
1 (
FAULT
)
2 (
CONST
SP
7)
3 (
LAST
SPEED
)
Set for appropriate drive
response.
3019
COMM
FAULT
TIME
Set time delay before acting on a communication loss.
Drive parameter
Protocol reference
0102
SPEED
0103
OUTPUT
FREQ
0104
CURRENT
0105
TORQUE
0106
POWER
0107
DC
BUS
VOLTAGE
0109
OUTPUT
VOLTAGE
0301
FB
CMD
WORD
1 – bit 0 (STOP)
0301
FB
CMD
WORD
1 – bit 2 (REV)
0118
DI
1-3
STATUS
– bit 0 (DI3)
Summary of Contents for ACQ550-x1-06A6-2
Page 1: ...ACQ550 User s Manual ACQ550 U1 Drives 1 200 hp ...
Page 4: ......
Page 10: ...10 ACS550 U1 User s Manual Table of contents ...
Page 42: ...42 ACQ550 U1 User s Manual Start up control with I O and ID Run ...
Page 56: ...56 ACQ550 U1 User s Manual Control panel ...
Page 68: ...68 ACQ550 U1 User s Manual Application macros ...
Page 250: ...250 ACQ550 U1 User s Manual Fieldbus adapter ...
Page 266: ...266 ACQ550 U1 User s Manual Maintenance ...
Page 314: ...314 ACQ550 U1 User s Manual Index ...