ACH580 E-Clipse bypass and packaged drive user manual
27
Control panel
Control panel
Bypass control
The bypass control panel features:
Power On Indication
The
Ready (Power On) indication
is provided by the bypass control panel. The
bypass control panel display will be illuminated and text will be displayed when the
disconnect switch or circuit breaker is closed and control power is applied to the
bypass.
Enabled LED
The
Enabled LED
is illuminated green under the following conditions:
• Both the Start Interlock(s) and Run Permissive contacts are closed.
• The Start Interlock contact(s) are closed with no Start command present.
The Enabled LED flashes green if the Run Permissive contact is open, the Start
Interlock contact(s) are closed, and Start command is present.
The Enabled LED is illuminated red when the Start Interlock contact(s) are open.
Motor Run LED
The
Motor Run LED
is illuminated green when the motor is running in either bypass
mode or in drive mode. The Motor Run LED flashes green to indicate the system has
been placed in an Override condition.
E-CLIPSE BYPASS CONTROL
ESC
ENTER
AUTO
OFF/RESET
HAND
DRIVE
BYPASS
ENABLED
SELECTED
FAULTED
MOTOR RUN
Down
Enabled LED
Drive and Bypass
Selected/Faulted LEDs
Drive/Bypass Select Keys
Motor Run LED
OFF/Reset Key
ON/Hand Key
Enter
Up
LCD Display
Auto Key
Escape
“Power On Indication”
(Display Illuminated)
Summary of Contents for ACH580 Series
Page 2: ......
Page 11: ...ACH580 BCR BDR VCR VDR E Clipse Bypass Drives 1 200 HP ...
Page 35: ...26 ACH580 E Clipse bypass and packaged drive user manual Installation ...
Page 43: ...34 ACH580 E Clipse bypass and packaged drive user manual Start up ...
Page 67: ...58 ACH580 E Clipse bypass and packaged drive user manual Application macros ...
Page 193: ...184 ACH580 E Clipse bypass and packaged drive user manual Fieldbus adapter ...
Page 207: ...198 ACH580 E Clipse bypass and packaged drive user manual Diagnostics ...
Page 229: ...220 ACH580 E Clipse bypass and packaged drive user manual Technical data ...
Page 231: ...ACH580 PCR PDR Packaged Drives with Disconnect 1 200 HP ...
Page 243: ...234 ACH580 E Clipse bypass and packaged drive user manual Installation ...
Page 256: ......