ACH580 Installation, Operation and Maintenance Manual
81
ACH580-01 Installation
Maintenance
WARNING!
Read
on page
before performing any maintenance
on the equipment. Ignoring the safety instructions can cause injury or death.
Maintenance schedule
Recommended maintenance intervals and component replacements are based on
specified operational and environmental conditions. ABB recommends annual drive
inspections to ensure the highest reliability and optimum performance.
Note:
Long term operation near the maximum specified ratings or environmental
conditions may require shorter maintenance intervals for certain components. Consult your
local ABB Service for maintenance recommendations at:
www.abb.com/searchchannels
Description of symbols
Recommended annual actions by the user
Recommended maintenance actions by the user
Action
Description
I
Inspection
(visual inspection and maintenance action if needed)
P
Performance
of on/off-site work (commissioning, tests, measurements or other work)
R
Replacement
Action
Description
P
Quality of supply voltage
I
Spare parts
P
Capacitor reforming for spare drives and spare capacitors (page
)
I
Tightness of terminals
I
Dustiness, corrosion or temperature
P
Heat sink cleaning (page
Component Replacement
Years from start-up
Instruction
3
6
9
12 15 18 21
Cooling
Fans, IP21 (UL (NEMA) Type 1) frames R1 to R9
Main cooling fans R1...R5
R
R
R1…R4: page
,
R5…R8: page
,
R9: page
Main cooling fans R6...R9
R
R
Auxiliary cooling fan for circuit boards
R
R
R5…R9: page
Fans, IP55 (UL (NEMA) Type 12) frames R1 to R9
Main cooling fans R1...R5
R
R
R
R1…R4: page
,
R5…R8: page
,
R9: page
Main cooling fans R6...R9
R
R
Auxiliary cooling fan for circuit boards R1...R2
R
R
R
R1…R2: page
,
R3: page
R4: page
R5…R9: page
Auxiliary cooling fan for circuit boards R3...R9
R
R
Second auxiliary cooling fan
R
R
R8 and R9: page
Aging
Control panel battery
R
R
page