Safe torque off function 353
Acceptance test procedure
After wiring the Safe torque off function, validate its operation as follows.
If a CPTC-02 module is installed, refer to its documentation.
Action
WARNING!
Follow the
. If you ignore them,
injury or death, or damage to the equipment can occur.
Ensure that the drive can be run and stopped freely during start-up.
Stop the drive (if running), switch the input power off and isolate the drive from the
power line by a disconnector.
Check the Safe torque off circuit connections against the wiring diagram.
Close the disconnector and switch the power on.
Test the operation of the STO function when the motor is stopped.
• Give a stop command for the drive (if running) and wait until the motor shaft is at a
standstill.
Ensure that the drive operates as follows:
• Open the STO circuit. The drive generates an indication if one is defined for the
‘stopped’ state in parameter
31.22
(see the firmware manual).
• Give a start command to verify that the STO function blocks the drive’s operation.
The drive generates a warning. The motor should not start.
• Close the STO circuit.
• Reset any active faults. Restart the drive and check that the motor runs normally.
Test the operation of the STO function when the motor is running.
• Start the drive and ensure the motor is running.
• Open the STO circuit. The motor should stop. The drive generates an indication if
one is defined for the ‘running’ state in parameter
31.22
STO indication run/stop
(see the firmware manual).
• Reset any active faults and try to start the drive.
• Ensure that the motor stays at a standstill and the drive operates as described
above in testing the operation when the motor is stopped.
• Close the STO circuit.
• Reset any active faults. Restart the drive and check that the motor runs normally.
Summary of Contents for ACH580-01 Series
Page 1: ...ABB DRIVES FOR HVAC ACH580 01 drives 0 75 to 250 kW 1 to 350 hp Hardware manual...
Page 2: ...Related documents are listed on page 27...
Page 4: ......
Page 14: ...14 Table of contents...
Page 24: ...24 Safety instructions...
Page 34: ...34 Introduction to the manual...
Page 52: ...52 Operation principle and hardware description...
Page 112: ...112 Guidelines for planning the electrical installation...
Page 122: ...122 Electrical installation IEC IEC R6 R9 Screw A EMC DC B EMC AC C VAR 3 B 3 A 4 C...
Page 156: ...156 Electrical installation IEC IEC R4 0 5 0 6 N m 0 4 lbf ft 7 4 3 8 11 5 9 11 6 10 8 4...
Page 157: ...Electrical installation IEC 157 IEC R5 4 6 11 11 10 4 3 5 7 8 9 0 5 0 6 N m 0 4 lbf ft 4 8...
Page 160: ...160 Electrical installation IEC IEC R3 R5 R1 R2 3 2 3 4 6 6 7 7 4 5 5...
Page 210: ...210 Electrical installation North America UL NEC R4 4 lbf ft 7 4 3 11 5 9 11 6 10...
Page 211: ...Electrical installation North America 211 UL NEC 8 R5 4 6 11 11 10 3 5 7 9 0 4 lbf ft 4...
Page 214: ...214 Electrical installation North America UL NEC R3 R5 R1 R2 3 2 3 4 6 6 7 7 4 5 5...
Page 222: ...222 Electrical installation North America UL NEC...
Page 242: ...242 Maintenance and hardware diagnostics...
Page 245: ...Technical data 245 See definitions and notes on page 247...
Page 308: ...308 Technical data...
Page 310: ...310 Dimension drawings Frame R1 IP21 UL Type 1 3AXD10000601652...
Page 311: ...Dimension drawings 311 Frame R1 IP55 UL Type 12 3AXD10000601699...
Page 312: ...312 Dimension drawings Frame R1 IP55 F278 UL Type 12 3AXD10000649451...
Page 313: ...Dimension drawings 313 Frame R2 IP21 UL Type 1 3AXD10000602398...
Page 314: ...314 Dimension drawings Frame R2 IP55 UL Type 12 3AXD10000602401...
Page 315: ...Dimension drawings 315 Frame R2 IP55 F278 UL Type 12 3AXD10000649654...
Page 316: ...316 Dimension drawings Frame R3 IP21 UL Type 1 3AXD10000602466...
Page 317: ...Dimension drawings 317 Frame R3 IP55 UL Type 12 3AXD10000602519...
Page 318: ...318 Dimension drawings Frame R3 IP55 E223 UL Type 12 3AXD10000649130...
Page 319: ...Dimension drawings 319 Frame R3 IP55 F278 F316 UL Type 12 3AXD10000649130...
Page 320: ...320 Dimension drawings Frame R4 IP21 UL Type 1 3AXD10000332430...
Page 321: ...Dimension drawings 321 Frame R4 IP55 UL Type 12 3AXD10000427933...
Page 322: ...322 Dimension drawings Frame R4 IP55 E223 UL Type 12 3AXD10000649283...
Page 323: ...Dimension drawings 323 Frame R4 IP55 F278 F316 UL Type 12 3AXD10000649283...
Page 324: ...324 Dimension drawings Frame R5 IP21 UL Type 1 3AXD10000412280...
Page 325: ...Dimension drawings 325 Frame R5 IP55 UL Type 12 3AXD10000415964...
Page 326: ...326 Dimension drawings Frame R5 IP55 E223 UL Type 12 3AXD10000687928...
Page 327: ...Dimension drawings 327 Frame R5 IP55 F278 F316 UL Type 12 3AXD10000687928...
Page 328: ...328 Dimension drawings Frame R6 IP21 UL Type 1 3AXD10000258705...
Page 329: ...Dimension drawings 329 Frame R6 IP55 UL Type 12 3AXD10000330667...
Page 330: ...330 Dimension drawings Frame R7 IP21 UL Type 1 3AXD10000258995...
Page 331: ...Dimension drawings 331 Frame R7 IP55 UL Type 12 3AXD10000330932...
Page 332: ...332 Dimension drawings Frame R8 IP21 UL Type 1 3AXD10000287670...
Page 333: ...Dimension drawings 333 Frame R8 IP55 UL Type 12 3AXD10000332446...
Page 334: ...334 Dimension drawings Frame R9 IP21 UL Type 1 3AXD10000287428...
Page 335: ...Dimension drawings 335 Frame R9 IP55 UL Type 12 3AXD10000334310...
Page 336: ...336 Dimension drawings...
Page 362: ...362 Safe torque off function...
Page 388: ...388 Optional I O extension modules...