ACH550-UH User’s Manual
Parameters
8128
AUX START ORDER
1, 2
1
1 (
EVEN
RUNTIME
)
Sets the start order of the auxiliary motors.
1 =
EVEN
RUNTIME
– Time sharing is active. Evens out the cumulative run time of the auxiliary motors. The start order
depends on the run time: The auxiliary motor whose cumulative run time is shortest is started first, then the motor
whose cumulative run time is the second shortest etc. When the demand drops, the first motor to be stopped is the
one whose cumulative run time is longest.
2 =
RELAY
ORDER
– The start order is fixed to be the order of the relays.
Group 81: PFA Control
Code Description Range
Resolution
Default