![ABB ACH550-01 User Manual Download Page 397](http://html.mh-extra.com/html/abb/ach550-01/ach550-01_user-manual_2924397.webp)
Technical data
385
ACH550 User's Manual
Motor cable length
The table below shows the maximum motor cable lengths for
400 V drives with different switching frequencies. Examples for
using the table are also given.
Under heading “Operational limits”, the “Basic unit” columns
define the cable lengths with which the basic drive unit works
without problems within the drive specification, without installing
any further options. Column “With du/dt filters” defines the cable
lengths when an external du/dt filter is used.
The columns under heading “EMC limits” show the maximum
cable lengths with which the units have been tested for EMC
emissions. The factory guarantees that these cable lengths
meet the EMC standard requirements.
If external sine filters are installed, longer cable lengths can be
used. With sine filters the limiting factors are the voltage drop of
the cable, which has to be taken into account in engineering, as
well as the EMC limits (where applicable).
The default switching frequency is 4 kHz.
WARNING!
Using a motor cable longer than specified in the
table above may cause permanent damage to the drive.
Maximum cable lengths (400 V)
Frame
size
EMC limits
Operational limits
Second environment
(category C3
1
)
First environment
(category C2
1
)
Basic unit
With
du/dt
filters
1 kHz 4 kHz 8 kHz 1 kHz 4 kHz 8 kHz 1/4 kHz
8/12
kHz
R1
300
300
300
300
300
300
100
100
150
R2
300
300
300
300
100
30
200
100
250
R3
300
300
300
300
75
75
200
100
250
R4
300
300
300
300
75
75
200
100
300
R5
100
100
100
100
100
100
300
150
2
300
R6
100
100
3
100
100
3
300
150
2
300
1
See the new terms in section
IEC/EN 61800-3 (2004) Definitions
on page
2
12 kHz switching frequency is not available.
3
Not tested.
Sine filters further extend the cable lengths.
Summary of Contents for ACH550-01
Page 1: ...ACH550 User s Manual ACH550 01 Drives 0 75 110 kW ACH550 UH Drives 1 150 HP ABB ...
Page 10: ...Update Notice 8 ...
Page 12: ......
Page 18: ...6 ACH550 User s Manual ...
Page 50: ...38 Preparing for installation ACH550 User s Manual ...
Page 325: ...313 ACH550 User s Manual ...
Page 358: ...346 ACH550 User s Manual ...
Page 409: ...Technical data 397 ACH550 User s Manual Frame size R1 IP54 UL Type 12 ...
Page 410: ...398 Technical data ACH550 User s Manual Frame size R2 IP54 UL Type 12 ...
Page 411: ...Technical data 399 ACH550 User s Manual Frame size R3 IP54 UL Type 12 ...
Page 412: ...400 Technical data ACH550 User s Manual Frame size R4 IP54 UL Type 12 ...
Page 413: ...Technical data 401 ACH550 User s Manual Frame size R5 IP54 UL Type 12 ...
Page 414: ...402 Technical data ACH550 User s Manual Frame size R6 IP54 UL Type 12 ...
Page 415: ...Technical data 403 ACH550 User s Manual Frame size R1 IP21 UL Type 1 ...
Page 416: ...404 Technical data ACH550 User s Manual Frame size R2 IP21 UL Type 1 ...
Page 417: ...Technical data 405 ACH550 User s Manual Frame size R3 IP21 UL Type 1 ...
Page 418: ...406 Technical data ACH550 User s Manual Frame size R4 IP21 UL Type 1 ...
Page 419: ...Technical data 407 ACH550 User s Manual Frame size R5 IP21 UL Type 1 ...
Page 420: ...408 Technical data ACH550 User s Manual Frame size R6 IP21 UL Type 1 ...
Page 453: ......