
3.1.5.2
Transitions between SM560-S states
ID*
From
To
Description
(1)
INIT
RUN
n
Initialization was successful
n
Boot project is available and there is no con-
figuration error or any other serious or fatal
error.
(2)
RUN
INIT
Powering off/on or
“reboot”
PLC Browser com-
mand from PM5xx Non-safety CPU
(3)
INIT
DEBUG STOP
n
Initialization was successful
n
No boot project is available or configuration
error E3
n
Switch address 0xFF was set on SM560-S
(4)
DEBUG STOP
INIT
Powering off/on or “reboot” PLC Browser com-
mand from PM5xx Non-safety CPU
(5)
INIT
SAFE STOP
n
Fatal error E1 or serious error E2 was identi-
fied during the initialisation
n
Unsuccessful firmware or boot code update
(6)
SAFE STOP
INIT
Powering off/on or
“reboot”
PLC Browser com-
mand from PM5xx Non-safety CPU
(7)
RUN
DEBUG RUN
CoDeSys-Safety online service
“Toggle
breakpoint”
,
“Write values”
,
“ Force values”
or
“Single cycle”
was used.
(8)
DEBUG STOP
SAFE STOP
Fatal error E1 or serious error E2 was identified
(9)
RUN
SAFE STOP
Fatal error E1 or serious error E2 was identified
(10)
RUN
DEBUG STOP
n
CoDeSys Safety online services
“Stop”
,
“Sourcecode download”
or
“Reset”
(various)
n
“Run”
button on PM5xx Non-safety CPU
(Non-safety CPU was in „Run“ state)
n
CoDeSys Non-safety online services
“Stop”
or
“Reset”
(various) on PM5xx
n
New safety application is loaded
(11)
DEBUG RUN
INIT
Powering off/on or
“reboot”
PLC Browser com-
mand from PM5xx Non-safety CPU
(12)
DEBUG RUN
SAFE STOP
Fatal error E1 or serious error E2 was identified
(13)
DEBUG RUN
DEBUG STOP
n
CoDeSys Safety online services
“Stop”
or
“Reset”
(various)
n
“Run”
button on PM5xx Non-safety CPU
(Non-safety CPU was in „Run“ state)
n
CoDeSys Non-safety online services
“Stop”
or
“Reset”
(various) on PM5xx
n
Breakpoint was reached during debugging
n
At the end of the Safety CPU cycle in “Single
cycle” debugging mode
n
New safety application is loaded
AC500-S Safety Modules
SM560-S Safety CPU > SM560-S module states
30.03.2017
AC500-S
50