![ABB AC500-S Safety User Manual Download Page 209](http://html.mh-extra.com/html/abb/ac500-s/ac500-s_safety-user-manual_2916209.webp)
DANGER!
If
“Update Device …”
function was used on Safety modules, then a full functional testing of
all parts of the safety-oriented application has to be performed. This test must be carried out
with the machine in its final configuration including mechanical, electrical and electronic com-
ponents, sensors, actuators and software.
NOTICE!
The user can later on verify using CoDeSys Safety menu item
“Online
è
Check boot project in PLC”
that offline CoDeSys safety project and the boot project on the
Safety CPU are identical (File name, Change date, Title, Author, Version, Description and
CRC).
The same comparison can be done with another boot project saved on the PC using
“Online
è
Check boot project in file system”
menu item.
Note that before the boot project is created offline on the PC for a backup and later
usage, the boot project has to be loaded at least once to the SM560-S Safety CPU.
It is highly recommended to execute “Clean All” , “Rebuild All” commands from CoD-
eSys Safety “Project” menu before downloading the safety program to SM560-S
Safety CPU.
NOTICE!
Remember that Non-safety CPU takes part in iParameter transfer to F-Devices, thus, you
shall not only download your safety application program to Safety CPU, but also in a similar
way (
Ä
AC500 User Documentation
for details) download Non-safety program from CoD-
eSys Non-Safety to Non-Safety CPU and create a boot project for PM5xx Non-Safety CPU.
If you do not follow the recommendation above, you may face configuration error or passiva-
tion of some F-Devices.
DANGER!
Do not use
“Write file to PLC”
command for SM560-S because it may lead to the loss of
important user information or load of corrupted data on SM560-S Safety CPU.
4.3.7 Checking of program and system configuration
Check your program and system configuration. Use "Checklist for creation of safety application pro-
gram" for program verification.
It is important that you are able to successfully fill out "Checklist for creation of safety application program"
Chapter 6.2 “Checklist for creation of safety application program” on page 406
program shall be approved without a positively completed "Checklist for creation of safety application pro-
gram". If some items from the "Checklist for creation of safety application program" cannot be fulfilled, then a
proper explanation shall be provided in the Comment section.
Configuration and programming
System configuration and programming > Checking of program and system configuration
30.03.2017
AC500-S