Section 2 Installation
Installing the FOUNDATION Fieldbus H1 Interface, CI852/TP852
3BSE 027 941 R301
69
Installing the FOUNDATION Fieldbus H1 Interface,
CI852/TP852
The CI852 is powered from the processor unit via the CEX-bus and requires
therefore no additional external power source. No field device on the FF H1 bus is
powered from the CI852.
An AC 800M Controller connected to a CI852 constitutes a FOUNDATION
Fieldbus linking device.
Use the following procedure to install the CI852/TP852:
1.
Mount the unit onto the DIN-rail, see
Mounting AC 800M Units onto DIN-Rail
on page 49 and
Installing the PM8xx/TP830 Processor Unit in Single
2.
Install a connector on the FOUNDATION Fieldbus cable. Connect the cable
screen to the ground terminal within the connector to ground the screen via
CI582.
3.
Connect the FOUNDATION Fieldbus cable to the contact on the baseplate.
FOUNDATION Fieldbus H1 Connection
Connect the FF H1 bus to the male DB9 connector located on the TP852 Baseplate.
The use of shielded twisted pair cables for FOUNDATION Fieldbus is
recommended (see
Appendix C, Recommended Components
Table 11. CI852 and TP852 FOUNDATION Fieldbus Connector
Pin
Designation
Description
1–5
–
Not used
6
FB-P
Receive/transmit data line, positive polarity
7
FB-N
Receive/transmit data line, negative polarity
8–9
–
Not used
Summary of Contents for AC 800M
Page 1: ...ControlIT AC 800M Version 2 1 Controller Hardware Hardware and Operation...
Page 2: ......
Page 3: ...Controller Hardware Hardware and Operation ControlIT AC 800M Version 2 1...
Page 10: ...7DEOH RI RQWHQWV 10 3BSE 027 941 R301...
Page 20: ...Related Documentation About This Book 20 3BSE 027 941 R301...
Page 26: ...Operating Environment Safety Summary 26 3BSE 027 941 R301...
Page 42: ...Product Release History Section 1 Introduction 42 3BSE 027 941 R301...
Page 108: ...Powering from an External 24 V DC Source Section 3 Configuration 108 3BSE 027 941 R301...
Page 118: ...Verification of Redundant CPU Section 4 Operation 118 3BSE 027 941 R301...
Page 212: ...Low Voltage Directive LVD Appendix D Directive Considerations 212 3BSE 027 941 R301...
Page 214: ...Hazardous Location Approval Appendix E Standards 214 3BSE 027 941 R301...
Page 228: ...QGH 228 3BSE 027 941 R301...
Page 229: ......