Table 4: AC voltage tests
Data
Voltage
Duration
24 V circuits (supply, 24 V inputs/outputs), when electri-
cally isolated from other circuitry
350 VAC
60 s
CS31 interface from other circuitry
350 VAC
60 s
Ethernet
350 VAC
60 s
ARCNET
350 VAC
60 s
COM interfaces, electrically isolated
350 VAC
60 s
Enabling input, electrically isolated
350 VAC
60 s
1.3.1.4
Power Supply Units
For the supply of devices, use power supply units according to PELV specification.
1.3.1.5
Electromagnetic compatibility
Table 5: Immunity
Data
Value
Immunity against electrostatic discharge
(ESD)
According to EN 61000-4-2, zone B, criterion
B
-> Interference voltage with air discharge
8 kV
-> Interference voltage with contact discharge 4 kV
ESD with communication connectors
Ensure that any electrostatic charge is dis-
charged prior to contact with the communica-
tion connectors (e.g. by touching an earthed
metal object). Otherwise malfunctions may
occur.
ESD module carrier connectors
Do not touch the plug connecting the module
carrier on the bottom side of the device.
ESD external coupler interface
Do not touch the plug to the flat ribbon cable.
Immunity against the influence of radiated
interference (CW radiated)
According to EN 61000-4-3, zone B, criterion
A
-> Test field strength
10 V/m (except ITU transmission bands 87…
108 MHz, 174…230 MHz and 470…790 MHz
-> 3 V/m)
-> Maximum temporary deviation during irradi-
ation
Analog current output signals max. 1.5 %.
Devices affected:
07AC91-AD, 07AC91-AD2,
07KT94-ARC-AD, 07KT98-ARC-AD,
07KT98-ARC-DP-AD, 07KT98-ARC-ETH-AD,
07KT98-ETH-DP-AD, 07KT98-ARC-ETH-DP-
AD
Immunity against transient interference vol-
tages (burst)
According to EN 61000-4-4, zone B, criterion
B
-> Voltage supply
2 kV
-> Enabling input
2 kV
AC31 Adapters
System data and CS31 bus system data > System data of the AC31 adapters
2018/09/24
3ADR010122, 8, en_US
6