Loop Detail Displays
Section 3 CCF Displays
32
3BUR002418-600 A
Loop Detail Displays
The Loop Detail Display provides the means to manipulate tunable parameters. The
information available on this display varies according to the loop type: Control,
Continuous, PID, and Device.
Control and PID Loops
The Loop Detail Display for a PID loop,
, shows the measured value,
setpoint value, and output value trends for a loop. A reduced or standard size
faceplate is used to modify the setpoint and output values. The trend graph shows up
to 600 points (traces start when the window is displayed). The data is based on CCF
trend data.
The trend
Refresh
rate on the Loop Detail page, allows you to change the rate at
which a trend graph is updated. Select
Refresh
to get the
Change Refresh Rate
dialog where you can change this rate to any integer number from 1 to 120 seconds,
the default value is 1. After changing the Refresh value, the plot restarts and the
trend is refreshed at the new rate.
The Loop Detail Display also provides the means to set the following loop
parameters:
•
Loop setup values, including Phase, Scan Rate, Loop Mode, and Trend Rate.
•
Tuning parameters, including Gain, Reset, and Preact.
•
Alarm configuration conditions:
–
Alarm Post.
–
Alarm Check.
–
Engineering Deadband.
–
Output Deadband.
–
Deviation Deadband.
Generally, users with Operator authority have read-only access to the Loop Detail
Display. Control/tuning functions are restricted to System Engineers. The
authority assignment for functions associated with this display can be changed as
described in the Objects and Access Rights section of
System 800xA
Configuration (3BDS011222*)
.
Summary of Contents for Ability 800xA Series
Page 1: ...Power and productivity for a better worldTM 800xA for MOD 300 Operation System Version 6 0 ...
Page 2: ......
Page 3: ...800xA for MOD 300 Operation System Version 6 0 ...
Page 14: ...Table of Contents 14 3BUR002418 600 A ...
Page 74: ...Area Graphic Display Section 3 CCF Displays 74 3BUR002418 600 A ...
Page 102: ...Batch Connectivity to M0D 300 Section 4 TCL Displays 102 3BUR002418 600 A ...
Page 120: ...TLL Messages Section 5 TLL Displays 120 3BUR002418 600 A ...
Page 212: ...Viewing Abnormal State on MOD Loop Displays Section 8 Operation Examples 212 3BUR002418 600 A ...
Page 320: ...BRKPTS Appendix A Runtime Templates 320 3BUR002418 600 A ...
Page 322: ...Updates in Revision Index A 322 3BUR002418 600 A ...
Page 330: ...Index 330 3BUR002418 600 A ...
Page 331: ......